Economy INN Reconstruction
4805 South Old State Road 37
Bloomington IN 47401
County MONROE
Project Type New   Addition Y Alteration   Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 8123492580 Email: [email protected]
Local Fire Official 
8123492580 Email: [email protected]
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IBC - 903.2.8
Conditions: A new R-1 Occupancy 4-unit motel Type VB construction of 1,428 sf, that is being rebuilt  based upon being razed from a tornado last year will not be provided with an automatic fire  suppression system. The attached existing 2-story office/apartment building will be  separated by 2-hour fire wall. 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. The attached existing 2-story office/apartment building will be separated from motel by 2- hour fire wall. 
2.  Each unit will be separated with a 1-hour fire barrier in lieu of the required 1-hour fire  partition. Each fire barrier will extend through crawl space up to roof deck.
3.  Each unit will be provided with an emergency escape and rescue window opening not  required by Section 1029.1.  
4.  Travel distance to an exit is 21 feet. 
5.  The code of record did not require a fire   suppression system. 
6.  The Building Department (Bobby LaRue) and Fire  
Department (George Cornwell) has been consulted and are aware of the variance.
 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
  Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
Facts: The owner's undue hardship involves the building was not required to be provided with a fire  suppression system under code of record. Additionally, based upon being razed by tornado  wasn¿t insured for modifications for newer code editions that require fire suppression.