Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IMC 1107.3 & 1107.5.3
Conditions: As of right now, there is not a very good path forward in addressing A2L provisions with the  current Indiana Mechanical Code, chapter 11. The two code sections mentioned above will  satisfy A2L requirements, but can be very costly, problematic from an installation perspective  and would require complicated engineering judgements as well. There is a path forward to  mitigate these issues, which has been met with great success in many different jurisdictions  throughout the nation. A code modification is requested to substitute chapter 11 of the current Indiana Mechanical Code with ASHRAE 15-2022. 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: ASHRAE 15, 2022 affectively addresses all A2L concerns from a safety perspective,  constructability perspective and installation perspective. 
If we can successfully get the code modification approved, we could then run refrigerant  concentration limit calculations and as long as we do not exceed the RCL values for R-32 &  R-454B refrigerant as outlined in ASHRAE 34-2022, we can keep lineset chases as-is in the  building without having to add a fire-rated shaft enclosure. We have had very little calculations fail, and it typically only occurs in a very small studio apartment. 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
 
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: Option #1: Per 2014 Indiana Mechanical Code, section 1107.3, a rigid or flexible metal  enclosure or pipe ducts would have to be provided for soft, annealed copper tubing. This is  not the most practical solution as it would require engineering judgements and can be  problematic from an installation perspective.
Option #2: Per 2014 Indiana Mechanical Code, section 1107.5.3, hard copper piping may be  used. This is the preferred method out of the two, but is the more costly of the two.