Owner / Applicant Information
Josette Rider
Big Brothers Big Sisters of Northeast Indiana
1005 WEST RUDISELL BOULEVARD
FORT WAYNE IN 46807
Phone 2604561600
Email [email protected]
Submitter Information
Edwin Rensink
RTM Consultants Inc
6640 Parkdale Place
Indianapolis IN  
Phone 3173297700
Email [email protected]
Designer Information
Chris Stine, AIA
Design Collaborative
200 East Main Street
Fort Wayne IN  
Phone 2604224241
Email [email protected]
Project Information
Big Brothers Big Sisters North River
200 6th Street
Fort Wayne IN 46808
County ALLEN
Project Type New   Addition Y Alteration Y Existing   Change of Occupancy Y
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 2604497131 Email: [email protected]
Local Fire Official 
2604497131 Email: [email protected]
Phone:


Variance Details
Code Name:  Other Code (Not in the list provided)
1004.1.2, 2014 IBC
Conditions: The 2nd floor event space will have a posted occupant load of 300 in lieu of a calculated  occupant load.  The calculated occupant load is 449 when considering the entire floor area  of the space.  The variance request is to permit a posted maximum occupant load of 300.  The variance is requested in order to permit the building to be evaluated per Chapter 16 as a  Risk Category II versus Risk Category III.  An attachment to the online variance filing which  explains rationale for the variance based upon the 2012 IBC Commentary, a 2021 IBC code  change, and the commentary to ASCE 7, 2010 Edition.

The project will convert the building for use as new headquarters for Big Brothers and Big  Sisters, including gathering areas, offices, a 2nd floor event space, and related functions.   The project also proposes an addition on the southwest corner of the building consisting of  a stair and elevator with a small lobby.  The addition will connect the 1st and 2nd floors and  extend to serve a rooftop deck area.  The east half of the building was constructed in 1896,  with masonry exterior walls and wood floor and roof structure. The west half was added in  1929, with masonry exterior walls and concrete building structure.  The building is evaluated  per Chapter 34 as non-separated occupancies - A-2, A-3, B, and S-1 Occupancies.  The  building is Type IIIB Construction.  The building will be protected throughout with an automatic sprinkler system.    
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.   Per the attached floor plans, the space will be set up for a maximum of 288 in a table-and- chair setup.  Request for up to 300 accounts for service staff.  

2.   The exception to this section in the model code (deleted in Indiana) permits an occupant  load less than that determined by calculation where approved by the building official.  The  2026 Indiana Building draft as proposed will retain the model code language permitting a  reduced occupant load where approved by the building official.

3. The design, including existing building components comply with IBC requirements for  seismic design per Sec. 1613.5.3, IBC, regardless of occupant load or Risk Category.  Wind  design will comply with Risk Category II.  

4. Similar variances have been granted to permit an actual occupant load in lieu of a  calculated occupant load under a variety of circumstances including 24-08-54, 25-01-09, 25- 12-25, 24-06-18, 23-10-77, 25-01-09, 25-10-50, 24-08-17, 26-07-12, 25-04-72, 23-09-16, 22- 12-04b, 23-04-07, 21-06-01a, 21-08-53j, 21-10-38b, 20-09-03a, 19-12-63a, 16-01-28, 23-04-7, and others.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
  Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure

Facts: Though compliant with IBC requirements for seismic design per Sec. 1613.5.3, the existing  building does not meet requirements for wind design for a Risk Category III (but will for a Risk  Category II as requested).  A significant degree of structural bracing would be required for RC III, which cannot be easily accommodated in the existing construction.  Of note, the existing  building has performed well over time since constructed in 1896 and 1924 with no adverse  incidents during all weather events over the 100+ year historical time frame.