Project Information
Mixed Use Property for RCA Properties
2332 East Washington Street
Indianapolis IN 46201
County MARION
Project Type New   Addition   Alteration Y Existing Y Change of Occupancy  
Project Status F F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 3173278700 Email: [email protected]
Local Fire Official 
3173278700 Email: [email protected]
Phone:


Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IBC, 508.4
Conditions: The renovation is to convert the second floor to apartments, the first floor for retail. The  approved construction documents require a 2-hour fire-resistance-rated floor/ceiling  assembly per Table 508.4. Existing framing of 1 x 6 tongue and groove subfloor was also  existing over the 2 x 12 floor joists which are spaced at 16-inches o.c.. A 3/8-inch OSB  subfloor and adhered luxury vinyl plank (LVP) finish flooring were installed on the subfloor  before the discrepancy was identified. Because the finish floor is now installed, the  assembly cannot be completed exactly as tested without demolishing completed work.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: The approved construction documents require a 2-hour fire-resistance-rated floor/ceiling  assembly between constructed as UL Design L511, which specifies 1 x 6 tongue and groove  subfloor installed over 2 x 10 wood joists with a minimum 7/16¿ additional subfloor over the  T&G. A resilient channel with 2 layers of type X gypsum shall be installed to the bottom of the  existing joists. Before the discrepancy was identified, 3/8-inch OSB subfloor and adhered  LVP finish flooring were installed over the T&G subfloor; this subfloor does not match the  subfloor specified in the referenced UL design. Removing the installed subfloor and finish  flooring to rebuild the assembly exactly as tested would require demolition of completed finish  work. The Owner proposes to achieve equivalent fire-resistance performance by field- applying FlameOFF Fire Barrier Paint as per the manufacturer¿s requirements to obtain the  one hour application thickness to the underside of the Type C drywall membrane in the lower  B-Occupancies. A 7/8-inch resilient channel at 16 inches on center and two layers of 5/8- inch Type C gypsum wallboard to the bottom of the existing joists (ceiling for B-Occupancies  below).
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: The ceiling-side membrane (7/8-inch resilient channel at 16 inches on center and two layers of 5/8-inch Type C gypsum wallboard, joints staggered and fully finished) shall be installed  continuously across the assembly and extended to the enclosing construction; penetrations  shall be protected per Section 714 and draftstopped per Section 718 at all joist bays.
The intumescent coating is FlameOFF® Fire Barrier Paint, ICC-ES Listed (ESL-1191/ESL-1192) and UL Classified (UL Fire Resistance Directory R38327), tested per ASTM E119/UL 263 (fire  endurance) and ASTM E84/UL 723 (surface burning); it shall be applied per the  manufacturer's requirements for a 1-hour fire-resistance contribution on a drywall substrate  that has a 1-hour rating. The entire system, with larger joists, etc. will develop a similar  required rating.
Similar variances have been approved previously that provide for intumescent coatings for a  substitute in 2-hour assemblies: 17-07-46.