Project Information
Project Louie 2
1200 W. Sapphire Lane
MOORESVILLE NC 46158  -  0000
County MORGAN
Project Type New   Addition   Alteration   Existing   Change of Occupancy  
Project Status F F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 7653421060 Email: [email protected]
Local Fire Official 
7653421060 Email: [email protected]
Phone:


Variance Details
Code Name:  Other Code (Not in the list provided)
IBC 2021 Sect. 1110.2 Except.3
Conditions: To permit the use of two multi-gender toilet rooms serving a one-story data center facility,  less than 50% accessible. Previous variance approval: 26-04-23, use of 2021 IBC and  reference standards. IBC 2021 Section 1110.2, Exception 3 requires at least 50 percent of  clustered single-user toilet rooms to be accessible. The proposed design provides two  multi-gender toilet rooms, each containing one accessible compartment and four standard  compartments. The proposed configuration does not meet the 50 percent accessibility  requirement as applied to the toilet compartments.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: In lieu of strict compliance with the accessibility distribution requirement, each multi-gender  toilet room provides one fully accessible water closet compartment, fully enclosed  compartments for privacy, four total water closet compartments, and four lavatories. In total,  only four water closets are required by code, and the design provides two ADA-compliant  water closet compartments. Therefore, the design meets the required number of ADA stalls for the total number of code-required water closets. The proposed configuration provides  adequate fixture capacity, accessibility, privacy, and occupant accommodation for the  facility¿s low-density occupancy and no public access.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
 
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
  Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
Facts: Strict compliance would require reconfiguration of the proposed toilet room layout to provide  additional accessible compartments and/or separate toilet facilities. Due to the facility¿s low- density occupancy, no public access, and operational requirements, the proposed  configuration provides adequate fixture capacity and accessibility without compromising  health, safety, or privacy. Reconfiguration of the restroom layout at this stage would also  result in significant construction impacts, including redesign, coordination, and sequencing  of multiple trades. Such changes would create additional construction delays and could  adversely affect the project schedule and the timely usability and occupancy of the building  upon completion.
Variance Details
Code Name:  Other Code (Not in the list provided)
IPC Section 405.3.4
Conditions: To allow the water closet compartments within Restroom to be provided without individual  lavatories located within each compartment. Previous variance approval: 26-04-23, use of  2021 IBC and reference standards.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w

1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: The proposed design consists of a single shared restroom serving both sexes with multiple  fully enclosed water closet compartments. Each compartment contains only a water closet  and functions as a water closet compartment rather than a separate toilet room. Shared  lavatories are provided immediately outside the compartments and remain fully accessible to  all restroom users without exiting Restroom. The intent of Section 405.3.2 is to ensure that  handwashing facilities are conveniently available to users of toilet facilities. That intent is  satisfied by the proposed arrangement, as all lavatories are located within the same restroom environment and directly adjacent to the water closet compartments. Users do not leave the  restroom area prior to accessing handwashing facilities.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
 
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: Due to the facility¿s low-density occupancy, controlled access, and operational  requirements, the proposed restroom configuration with lavatories outside the individual water closet compartments provides adequate fixture capacity, accessibility, health, safety, and  privacy. Reconfiguring the restroom layout at this stage would require significant redesign,  trade coordination, and construction re-sequencing, resulting in additional cost and potential  delays to the project schedule. Requiring these changes would create a disproportionate  hardship without providing a meaningful benefit to the facility¿s occupants.

Variance Details
Code Name: 2012 Indiana Plumbing Cod, (675 IAC 16-1.4)
Section 405.3.2
Conditions: 675 IAC 16-1.4, 2012 Indiana Plumbing Code, Section 405.3.2 requires the required lavatory to be located in the same room as the required water closet in employee and public toilet  rooms. The proposed design provides water closets within fully enclosed compartments,  with the required lavatories located in the common restroom area immediately outside the  compartments
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: The proposed design consists of a single shared restroom serving both sexes with multiple  fully enclosed water closet compartments. Each compartment contains only a water closet  and functions as a water closet compartment rather than a separate toilet room. Shared  lavatories are provided immediately outside the compartments and remain fully accessible to  all restroom users without exiting Restroom. The intent of Section 405.3.2 is to ensure that  handwashing facilities are conveniently available to users of toilet facilities. That intent is  satisfied by the proposed arrangement, as all lavatories are located within the same restroom environment and directly adjacent to the water closet compartments. Users do not leave the  restroom area prior to accessing handwashing facilities
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: Due to the facility¿s low-density occupancy, controlled access, and operational  requirements, the proposed restroom configuration with lavatories outside the individual water closet compartments provides adequate fixture capacity, accessibility, health, safety, and  privacy.
Reconfiguring the restroom layout at this stage would require significant redesign, trade  coordination, and construction re-sequencing, resulting in additional cost and potential  delays to the project schedule. Requiring these changes would create a disproportionate  hardship without providing a meaningful benefit to the facility¿s occupants.
Variance Details
Code Name:  Other Code (Not in the list provided)
2014 InBC 1109.2
Conditions: 675 IAC 13-2.6, 2014 Indiana Building Code, Section 1109.2, Exception 3 requires that where  multiple single-user toilet rooms or bathing rooms are clustered at a single location, at least  50 percent, but not less than one room for each use at each cluster, shall be accessible.  The proposed design provides two multi-gender toilet rooms, each containing one  accessible compartment and four standard compartments. The proposed configuration does not meet the 50 percent accessibility requirement as applied to the toilet compartments.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:

DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: In lieu of strict compliance with the accessibility distribution requirement, each multi-gender  toilet room provides one fully accessible water closet compartment, fully enclosed  compartments for privacy, four total water closet compartments, and four lavatories. In total,  only four water closets are required by code, and the design provides two ADA-compliant  water closet compartments. Therefore, the design meets the required number of ADA stalls for the total number of code-required water closets. The proposed configuration provides  adequate fixture capacity, accessibility, privacy, and occupant accommodation for the  facility¿s low-density occupancy and no public access.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
 
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: Strict compliance would require reconfiguration of the proposed toilet room layout to provide  additional accessible compartments and/or separate toilet facilities. Due to the facility¿s low- density occupancy, no public access, and operational requirements, the proposed  configuration provides adequate fixture capacity and accessibility without compromising  health, safety, or privacy.
Reconfiguration of the restroom layout at this stage would also result in significant  construction impacts, including redesign, coordination, and sequencing of multiple trades.  Such changes would create additional construction delays and could adversely affect the  project schedule and the timely usability and occupancy of the building upon completion