Project Information
Highwater Marine Addition
4310 Middlebury Street
Elkhart IN 46516
County ELKHART
Project Type New   Addition Y Alteration   Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 5742938931 Email: [email protected]
Local Fire Official 
5742938931 Email: [email protected]
Phone:


Variance Details
Code Name:  Other Code (Not in the list provided)
507.3, 2014 IBC
Conditions: The proposed addition of 56,568 sq ft + existing area of approximately 62,000 sq ft existing  manufacturing facility will be designed as an unlimited area building but will not have 60 feet  of frontage for 8.8% of the building perimeter.  8.8% of the total building perimeter will have  42.5 feet along the west exterior wall of the addition.  Additionally, there is 54.5 feet from the  existing building at a tangent point to an existing building on the same property.  Code  requires 60 feet of open space surrounding a building designed as unlimited area.

The building is classified as F-1 Occupancy and Type IIB Construction.  The facility  manufactures boat seating and upholstery products.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.   The building will be protected throughout with a sprinkler system per NFPA 13.  The  building will be of noncombustible construction.
 
2.    Vehicle access will be provided around the perimeter of the combined new/existing  building.

3. NFPA 80A, Protection of Buildings from Exterior Fire Exposures, states in Sec. 5.6.3 that  where exposing buildings are protected throughout with an automatic sprinkler system, no  exposure hazard is considered to exist.

4. Based upon automatic sprinkler protection in the building, the minimum 42.5 feet of frontage, and fractional perimeter of the building lacking 60 feet of frontage, the proposed expansion of  the building will not be adverse to safety.

5. Similar variances have been approved for lack of 60 feet of separation under a variety of  circumstances, including 23-05-03, 26-06-71, 26-01-70, 26-02-09, 25-11-05, 25-02-34, 24- 07-07, 20-02-06, 19-10-23, 23-12-84, 23-05-24, 22-07-62, 22-01-28, 20-12-42, 19-01-28, 19- 10-23, 16-09-35a, 16-01-19, 18-05-30, 18-02-21, 16-07-55, 16-07-59, and 16-07-60.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
Y
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
 
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: Hardship is the restricted site from east to west.  The proposed construction cannot be  placed on the site to meet the 60 feet of frontage based upon configuration of the site and  maintaining building configuration to meet operational needs.