Owner / Applicant Information
Adam Berning
Red Gold
120 E. OAK STREET
ORESTES IN 46063
Phone 7655575500
Email [email protected]
Submitter Information
Christina Collester
RTM Consultants, Inc.
6640 Parkdale Place
Indianapolis IN  
Phone 3173297700
Email [email protected]
Designer Information
Joe E. Humbert
Project Design & Management Inc.
725 Airport North Office Park
Ft. Wayne IN  
Phone 2602134519
Email [email protected]
Project Information
Red Gold Orestes Migrant Housing Restroom Addition
120 E. Oak Street
Orestes IN 46063
County MADISON
Project Type New   Addition Y Alteration   Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 7656419541 Email: [email protected]
Local Fire Official 
7656419541 Email: [email protected]
Phone:


Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IBC 903.2.8
Conditions: The 2014 IBC requires an automatic sprinkler system installed in accordance with Section  903.3 shall be provided throughout all buildings with a Group R fire area. The new migrant  housing units at the existing facility will not be sprinklered.  A previous variance was granted  to omit sprinklers in the seasonal housing units.

This project is a remodel and addition to the existing residential units to include a bathroom  for each unit in Buildings "E" and "W" of 86 s.f per unit.

Sprinklers will not be added to the exisitng buildings.
 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.  There will be no increase in existing occupant Load designated to each sleeping unit.
 
2. Per NFPA 13R systems and residential areas of NFPA 13 systems, sprinklers can be  omitted from bathrooms less than 55 square feet The new bathroom area is less than 55 s.f  and would be otherwise exempt from the requirement for sprinklers.

3. Smoke detection are provided throughout in accordance with section 907.2.11.1 and will
be interconnected to provide an evacuation alarm throughout the building.

4. Each dwelling unit is provided with a door directly to the exterior.
 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
Y
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: The infrastructure at the site was not designed for automatic sprinklers in the housing units.  The method of protection being implemented is similar to the method used for townhouses  and as approved in previous migrant housing variances. Including 09-06-48 and 22-03-30.