Project Information
SMC Scottsburg Family Care
1366 N Gardner St Suite 140
Scottsburg IN 47170
County SCOTT
Project Type New   Addition   Alteration Y Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order?    
Violation Issued by: NA
Local Building Official
Phone: 8127221157 Email: [email protected]
Local Fire Official 
8127221157 Email: [email protected]
Phone:


Variance Details
Code Name:  Other Code (Not in the list provided)
2014 InBC Table 1018.1
Conditions: The corridors will not be fire-rated for the interior renovation of the medical office building.  Fire rated corridor construction is required for newly constructed corridors based upon the  corridor serving an occupant load of 30 or more and not being provided with an automatic  sprinkler system.

The project consists of an interior renovation of the Scottsburg Family Care medical office  building. As part of the renovation, the clinic will be creating additional exam rooms and  support spaces. The building is a single story of approximately 11,050 SF and is of Type IIIB  construction. The area of the interior renovation is approximately 4,600 SF. 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. A fire alarm system will be provided throughout the building - not required by code. 

2. Corridor smoke detection tied to the fire alarm system will be provided - not required by  code.

3. Maximum egress travel distance will be approximately 115 feet - code permits 200 feet  maximum.

4. The corridor system will be provided with four exits directly to the exterior.

5. The design complies with NFPA 101, Life Safety Code, Sec. 38.3.6, exc. 2, which permits  non-rated corridors in an office tenant space occupied by a single tenant.

6. Similar variances have been granted including 26-05-23, 26-01-38, 25-09-70, 25-07-42, 25- 02-17, 25-10-39, 23-07-39, 22-02-40, 22-09-20, 20-12-60, 18-02-15, 17-05-40, 13-03-36a, 13- 03-36b, 19-09-31, 19-08-70, 18-02-15, 18-02-29, 17-08-09, 19-06-71, 11-06-32, 12-10-28, and 13-03-45, 16-03-23, 16-06-56, 16-06-61, 15-01-33, 15-06-54, 16-07-11, and 16-07-27.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
Y
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
  Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
Facts: Imposition of the rule would require any newly constructed corridors to be fire rated corridors  along with associated fire rated doors and door closers. Much of the corridor system is  existing and non-rated. Typical everyday office use, doors will be in the open position which  would require additional door hold opens. Being that the building is a single tenant and being  provided with a fire alarm and corridor smoke detection, the proposed will not be adverse to  public health or safety.