Project Information
New Lodge Potato Creek State Park
25601 SR 4
NORTH LIBERTY IN 46554
County ST JOSEPH
Project Type New Y Addition   Alteration   Existing   Change of Occupancy  
Project Status F F=Filed U or Null=Unfiled
IDHS Issued Correction order?    
Violation Issued by: NA
Local Building Official
Phone: 5742359554 Email: [email protected]
Local Fire Official 
5742359554 Email: [email protected]
Phone:


Variance Details
Code Name:  Other Code (Not in the list provided)
2014 InBC Section 708.4
Conditions: The sleeping unit separation walls and corridor walls do not fully extend to the deck above  but terminate at the underside of the structural beams in several locations in the basement  level . Code requires that fire partitions extend to the underside of the deck above or to a fire  rated ceiling/floor assembly.

The project consists of the new Potato Creek State Park Lodge. The lodge will include  banquet and conference facilities, a restaurant, office spaces, game room, library, gift shop,  aquatic center and guest rooms. The area in question occurs in the basement level of the  guest rooms. This area is of Type IIB construction, R-1 Occupancy and a total of 3 stories in  height. The lodge is provided with automatic sprinkler protection throughout. 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. The beams will be provided with an intumescent coating providing a fire rating greater than  that required for the fire partitions.

2. The fire partitions are only required to be provided with a 30-minute fire rating since the  facility is provided with an automatic sprinkler system throughout.

3. A fire rated joint system will be provided where the fire partition meets the beam and where  the beam connects to the deck above. The required fire rating will be continuous to the deck  above.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
Y
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: The walls in question have already been framed and drywalled. MEP systems are installed in  the throughout the ceiling spaces creating difficulties in re-framing the walls. Imposition of the  rule would require taking down several MEP systems and the current walls in order to re- frame the walls in way to go around the beams. The intumescent coatings being provided on  the beams provide a greater fire rating than the required fire rating of 30 minutes. The required fire rating will be continuous to the deck above. The proposed design will not be adverse to  public health or safety.