Project Information
Thermo Dyne, Inc., Electronic Storage Warehouse
3709 Cassopolis Street
Elkhart IN 46154
County ELKHART
Project Type New   Addition Y Alteration   Existing Y Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 5743224846 Email: [email protected]
Local Fire Official 
5743224846 Email: [email protected]
Phone:


Variance Details
Code Name:  Other Code (Not in the list provided)
2014 InBC 903.3.1 
Conditions: An existing, single-story, F-1 Occupancy manufacturing facility of approximately 137,530 sf,  Type IIB construction will be incorporating a 3-story expansion (2nd-level is a mezzanine  serving the first floor, and floors 2 and 3 which are at, and above the roof line, respectively),  within the existing footprint. It is also of Type IIB construction of approximately 3,185 sf per  floor. The existing building is fully sprinklered with an NFPA 13 system. Per Table 503, an F-1  Occupancy of Type IIB Construction has a max allowable area of 15,500. However, per 507.3, this building has an unlimited area with a sprinkler system meeting 903.3.1.1, and  surrounded with 60-feet yards, of which it does. The building will be considered fully  sprinklered for compliance with other sections of the building code.
The tower walls are of 2-hour construction to the roof deck and include two means of egress to the ground floor as well as a LULA elevator. At each level there is sensitive electronic  equipment which can¿t become wet if a sprinkler should be triggered, nor can a chemical  suppression system be used due to the sensitivity of the equipment. The maximum travel  distance from the top floor to a point of egress at the vestibule of the tower is approximately  256-feet. There is a travel distance of approximately 85-feet to the nearest most point of  egress. The existing building has multiple points of egress around the entire facility.
 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: The variance request is to allow the 3-story tower to be included as part of that area, without a fire suppression system which would be required by Sec. 903.3.1.

1. The existing building, of Type II-B noncombustible construction, is protected with an  automatic fire suppression system per NFPA 13, meeting 903.3.1.1. The new tower shall have  a rated wall assembly from the ground floor to the roof of 2-hours in lieu of 1-hour. The  mezzanine may be enclosed per Section 502.3, Exception 5.
2. The floor areas of the mezzanine, or floors 2 and 3, will not be used to store combustible  materials.
3. The path of egress shall be marked on the ground floor, leading to a point of egress in  multiple directions.
4. Staff are not stationed within the tower on a permanent basis and only access the tower to  verify operations on an as needed basis and any equipment malfunctions that may need to be addressed.
5. The tower will be provided throughout with smoke detection, fire alarm notification devices  (horns/strobes) which are tied to the main fire alarm panel.
 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: The owner's undue hardship involves the damage that may occur to the equipment located  within the tower with a sprinkler system, meeting 903.3.1.1 or a chemical fire suppression  system, which can damage the intricate and delicate electronics.

Facts: The owner's undue hardship involves the damage that may occur to the equipment located  within the tower with a sprinkler system, meeting 903.3.1.1 or a chemical fire suppression  system, which can damage the intricate and delicate electronics.

Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IBC Sec. Table 1016.2
Conditions: An existing, single-story, F-1 Occupancy manufacturing facility of approximately 137,530 sf,  Type IIB construction will be incorporating a 3-story expansion (2nd-level is a mezzanine  serving the first floor, and floors 2 and 3 which are at, and above the roof line, respectively),  within the existing footprint. It is also Type IIB construction of approx. 3,185 sf per floor. The  existing building is fully sprinklered per 903.3.1.1. Per Sec. 507.3, F-1 Occupancy of Type IIB  Construction with sprinkler and 60-ft yard around the perimeter is allowed unlimited area with  a sprinkler system meeting 903.3.1.1. The building will be considered fully sprinklered for  compliance with other sections of the building code.
The tower has walls of 2-hour construction to the roof deck and includes 2 means of egress  to the ground floor. Each level has sensitive electronic equipment which can¿t become wet if  a sprinkler should be triggered, nor can a chemical suppression system be used due to the  sensitivity of the equipment. The allowable travel distance for an F-1 Occupancy per Table  1016.2 is 250-feet with a sprinkler system. The actual maximum travel distance from the top  floor to a point of egress at the vestibule of the tower is approximately 208-feet for the furthest  stair, and 158-feet for the nearest stair to the vestibule. There is a travel distance of  approximately 85-feet to the nearest most point of egress. The existing building has multiple  points of egress around the entire facility. As the tower has less than 50-occupants per floor  by calculation, the tower is only required to have one egress. If using the nearest stair and  calculating to the furthest point on the upper level, total travel distance to the vestibule is 193- feet, 2-inches. With the egress from the vestibule door to the nearest point of egress is  approx. 278-feet, 28-feet beyond the maximum allow. distance of 250-feet.
 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
 
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: The variance request is to allow the travel distance from most remote point in the top of the  tower to the nearest point of egress to extend to 278-feet. Once an occupant egresses from  the tower vestibule, the travel distance to the nearest point of egress is approximately 85-feet  which is covered by a sprinkler system meeting 903.3.1.1.

1. The existing building is protected with an automatic fire suppression system per NFPA 13,  meeting 903.3.1.1. The new tower shall have a rated wall assembly from the ground floor to the roof of 2-hours in lieu of 1-hour.

2. The path of egress shall be marked on the ground floor, leading to a point of egress in  multiple directions.

3. Staff are not stationed within the tower on a permanent basis and only access those areas  to verify operations on an as needed basis and any equipment malfunctions that may need to  be addressed. Occupancy is limited to only specific personnel involved with this project and  not all staff is granted access. There are no visitors or public allowed within the  manufacturing area.

4. Variances have been approved for the extended distances through rated wall assemblies  such as: 24-12-70(c), 25-08-34, 20-02-40(c), 20-09-39

5. The tower will be provided throughout with smoke detection, fire alarm notification devices  (horns/strobes) which are tied to the main fire alarm panel.
 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
Y

Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
 
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
  Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
Facts: 1. The owner's undue hardship involves the in ability for the systems to maintain the process  they are being design for if there is a reduction in equipment. The system needs this area for  the number of pieces of electronic equipment elements to function for the overall process.  Additionally, this will create a loss of revenue to reduce the height of the tower in order to  shorten the distance for travel. The required equipment is needed for the full operation and  must be located on each floor.

2. Providing a horizontal egress from the vestibule to the exterior egress is not possible due  to the ongoing processes currently being performed on the factory floor, as well as creating  an impasse for materials and staff to attend to their duties and/or equipment.