Project Information
SBN216 (SAB)
57500 Huckleberry Road 
New Carlisle AL 46552
County ST JOSEPH
Project Type New Y Addition   Alteration   Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 5742359554 Email: [email protected]
Local Fire Official 
5742359554 Email: [email protected]
Phone:


Variance Details
Code Name:  Other Code (Not in the list provided)
2014 InMC Section 1104.3.2
Conditions: The 2014 Indiana Mechanical Code (IMC) prohibits the use of A2L refrigerants, such as R-32, for human comfort applications. This creates a conflict with the requirements of the American Innovation and Manufacturing Act (AIM), signed into law on December 27, 2020, which  mandates the phase-down of high-GWP refrigerants and effectively requires the use of A1 or A2L refrigerants in commercial mechanical systems. The 2014 IMC does not address A2L  refrigerants, leading to a regulatory gap. To resolve this for the office building, we are  proposing a code alternate based on a more current edition of the International Mechanical  Code, along with compliance with the ASHRAE Standards 15 and 34, which explicitly address the classification and safe use of A2L refrigerants. 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: If the project is required to comply with the 2014 Indiana Mechanical Code, the use of an A2L  refrigerant such as R-32, will not be permitted, as these codes do not acknowledge or  address R-32 refrigerants in Chapter 11. However, due to the regulatory requirements  established by the AIM act, mechanical systems for this type building must now utilize R-32  refrigerants. Accordingly, we are proposing to base the project design on the most current  standards and guidance, including ASHRAE 15-2024 and ASHRAE 34-2024 recommendations  and the approved revisions in the upcoming 2027 International Mechanical Code. 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: Refrigerants recognized by the Indiana Mechanical Code will soon be prohibited by federal  law. Equipment accommodating the current refrigerants will no longer be manufactured as of  January 1, 2025, and may not be installed after January 1, 2026. Due to the currently adopted  codes in Indiana and the mandate to use A2L refrigerants, such as R-32 for human comfort  applications in commercial buildings, a code alternate is required to permit the use of R-32  refrigerants. Please refer to the attached supporting calculations for further details.