Owner / Applicant Information
Schrock Aaron
A & R Woodworking
16801 STATE ROAD 4
GOSHEN IN 46528
Phone 5743742366
Email [email protected]
Submitter Information
Kevin Finn
Kevin M. Finn, P.E., Inc.
815 Waterbury Park Dr.
Elkhart IN  
Phone 5745371300
Email [email protected]
Designer Information
Kevin Finn
Kevin M. Finn, P.E., Inc.
815 Waterbury Park Dr.
Elkhart IN  
Phone 5745371300
Email [email protected]
Project Information
A & R Woodworking
16801 SR 4
GOSHEN IN 46528
County ELKHART
Project Type New Y Addition   Alteration   Existing   Change of Occupancy  
Project Status F F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 5749714678 Email: [email protected]
Local Fire Official 
5749714678 Email: [email protected]
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
2014 InBC 903.2.4.1
Conditions: The F1 (Wood Operations) Occupancy will not be provided with an automatic fire  suppression system.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. The source for water for a sprinkler system is not available.
2. A 3-hour fire barrier will be provided to separate the F-1 Wood Shop from Motor Room.
3. Highly reflective photo luminescent exit signs will be installed at each exit door. 
4. Long-life battery-operated interlinked smoke and heat detectors will be installed throughout  building.
5. Fire extinguishers to be located as required throughout building.
6. Manual alarm bell(s) will be installed in designated locations. 
7. There will be no open flame allowed in wood shop area. 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: The building management has an in-house fire response system to extinguish any fire within  a 2-minute time period during operation.