Project Information
IU Health-Riley Retail Pharmacy Relocation
705 Riley Hospital Drive
Indianapolis IN 46202
County MARION
Project Type New   Addition   Alteration Y Existing   Change of Occupancy  
Project Status F F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 3173277526 Email: [email protected]
Local Fire Official 
3173277526 Email: [email protected]
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
1008.1.4.4, 2014 InBC
Conditions: A vertical security grille will not be located at a main exit. Instead the security grille will be  located at the exit access from a tenant space. 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: While the 2014 Indiana Building Code only permits vertical security grilles at the main exits in a Business Occupancy, NFPA 101 permits them as general part of the means of egress from a  tenant space of a Business Occupancy.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
Y
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
 
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: NFPA 101 is the nationally recognized standard for life safety in the heatlhcare environment.  The installation at this location for the retail pharmacy will fully comply with all requirements of  NFPA 101-2012.