Project Information
Indiana University Lilly Library Renovation
1200 E 7th St
BLOOMINGTON KY 47405
County MONROE
Project Type New   Addition   Alteration   Existing Y Change of Occupancy  
Project Status F F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 8123492580 Email: [email protected]
Local Fire Official 
8123492580 Email: [email protected]
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IBC Sect. 1003.2 & 1208.2
Conditions: The Lilly Library is being renovated and the existing floor to deck elevations in the book stack  areas (levels 4-7) are restricted mostly below 7'-6". Ductwork is being installed in these  locations that will require the elevation of the bottom of ductwork to be below 7'-6". IBC  Section 1003.2 and 1208.2 both require 7'6" minimum. See attached documents for installed  ductwork elevations. Previous variance for low head clearance in another portion of building  was submitted for this project (19-12-18, supporting docs attached).
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.  The building will be fully sprinkled with an NFPA 13 system as part of the project 
2.  The building will be protected with NPFA 72 fire alarm system with smoke detection  throughout as part of the project.
3. The commission has granted numerous variances for "low headroom clearance" under IBC section 1003.2 and 1208.2.
4. This was an existing condition, and the new ductwork is designed to be equal to or better  than (in regard to elevation) the existing ductwork installation (see attached pictures of  existing ductwork).
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
Y
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: 1.  Modification of the ceiling height would compromise the structure of the building.
2.  The condition has existed since the building was constructed over 62 years ago. It is  impossible to alter the existing floor to floor height of multiple stories in this portion of the  building