Owner / Applicant Information
John Reeder
Reeder Real Estate Properties, LLC
12802 CHAPEL SQUARE STREET
CARMEL IN 46032
Phone 3175903305
Email [email protected]
Submitter Information
Edwin Rensink
RTM Consultants Inc
6640 Parkdale Place
Indianaplis IN  
Phone 3173297700
Email [email protected]
Designer Information
Daniel Moriarity
Studio M Architecture and Planning
2 West Main Street
Carmel IN  
Phone 3178101502
Email [email protected]
Project Information
County Line Road Retail Building
2400 West County Line Road
Indianapolis IN 46217
County MARION
Project Type New Y Addition   Alteration   Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 3173275544 Email: [email protected]
Local Fire Official 
3173275544 Email: [email protected]
Phone:


Variance Details
Code Name:  Other Code (Not in the list provided)
507.5.1, 2014 IFC
Conditions: A fire hydrant connected to a water supply capable of providing required fire flow will not be  provided within 400 feet of the new 1-story 3,600 sq ft retail building.  The nearest public water supply capable of providing required fire flow is a City of Indianapolis water main located  2,600  feet to the east along County Line Road.
    
The building will be classified as M Occupancy and Type VB Construction. 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.   The building will be provided with a monitored fire alarm system, and provided with smoke  detection throughout - not required by code for this occupancy.  The system will provide an  automatic alarm in the event of fire.

2.   Based upon the size of the building and provision of two (2) exits, egress travel distance  will be a maximum of 60 feet.  The lack of a water supply for fire fighting is not a life safety  issue for building occupants.   

3. Fire extinguishers will be provided, as required.

4. Similar variances have been granted for buildings in Marion County without a public water  supply capable of the required fire flow where a monitored fire detection and alarm system is  provided, including 20-02-52, 18-02-33a, 17-05-56, 17-10-45, 17-09-55, 19-07-06, 16-12-49,  16-10-16, 14-01-40a, 13-04-30a, 12-12-49b, 10-04-55d.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
 
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: The nearest public water supply capable of supplying a fire hydrant is 2,600 feet from the site.  The estimate to bring the water supply to this site is $661,800.  The approximate project cost  otherwise is $600,000.