Project Information
Equity Vigo County
1001 W SR 246
 
TERRE HAUTE IN 47802
County VIGO
Project Type New Y Addition   Alteration   Existing   Change of Occupancy  
Project Status F F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 8124623365 Email: paul.mason@vigocounty.in.gov
Local Fire Official 
8124623365 Email: combinechief47@yahoo.com
Phone:


Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IBC Sec. 903.2.11.1
Conditions: A dry fertilizer storage building that is approximately 80 feet x 216 feet will not have openings  on 2 sides and will not be provided with an automatic sprinkler system. Openings are provided  along one long side (216 feet) of the building.  Code requires where openings are only  provided on one side and the opposite wall is more than 75 feet from the side with openings,  an automatic sprinkler system must be provided or openings must be provided on 2 sides.

The building is classified Type VB (Concrete structure with membrane roof) and was released as S-1 Occupancy.  The building is only used for storage of dry fertilizer that is nonflammable,  noncombustible and nontoxic.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or we
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. There are openings along one long side of the building. The requirement for opposite wall to  be within 75 feet is exceeded by 5 feet. 

2. The dry fertilizers stored are nonflammable, noncombustible, and nontoxic.

3. There will be very minimal occupants in the building - maximum anticipated 2 to 3 employees at any time.  Employees are only entering the building for loading/unloading fertilizer.

4. Based upon the general lack of fire hazard and very minimal occupancy of the building, the  lack of sprinkler protection will not be adverse to safety.

5. Similar variances have been granted, including 20-01-76 for Co Alliance Dry Fertilizer Building  and others for similar style salt storage 19-09-01 and 18-03-52(b).  
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty) because  of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty) because  of major operational problems in the use of the building or structure.
Y
Y Imposition of the rule would result in an undue hardship (unusual difficulty) because  of excessive costs of additional or altered construction elements.
  Imposition of the rule would prevent the preservation of an architecturally or a historically significant part of the building or structure.
Facts: Adding openings in other walls will defeat the purpose of the building for bulk storage of dry  fertilizers. It is also a cost hardship to add sprinklers while the fertilizer stored is all  nonflammable and noncombustible. It is estimated to cost over $200k to add sprinklers to the  building.  Additionally, fertilizer mixed with fire suppression water could cause environmental  contamination and create issues with cleanup operations..
Variance Details
Code Name:  Other Code (Not in the list provided)

2014 IBC Sec. 903.2.9
Conditions: A fertilizer storage building with approximately 17,000 sf fire area will not be provided with an  automatic sprinkler system. The dry fertilizer stored is nonflammable, noncombustible and  nontoxic.  Code requires sprinklers to be provided for S-1 fire area exceeding 12,000 square  feet. 

The building is classified Type VB (concrete walls with membrane roof structure) and was  released as S-1 Occupancy.  The building is only used for storage of fertilizer that is  nonflammable, noncombustible and nontoxic.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or we
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. The dry fertilizers stored are nonflammable, noncombustible, and nontoxic.

2. There will be very minimal occupants in the building - maximum anticipated 2 to 3 employees at any time.  Employees are only entering the building for loading/unloading fertilizer.

3. Based upon the general lack of fire hazard and very minimal occupancy of the building, the  lack of sprinkler protection will not be adverse to safety.

4. Similar variances have been granted, including 17-10-26 for Helena Chemical Dry Fertilizer  Plant and 18-01-48 for Shelby County Co-Op.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty) because  of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty) because  of major operational problems in the use of the building or structure.
Y
Y Imposition of the rule would result in an undue hardship (unusual difficulty) because  of excessive costs of additional or altered construction elements.
  Imposition of the rule would prevent the preservation of an architecturally or a historically significant part of the building or structure.
Facts: It is a cost hardship to add sprinklers while the fertilizer stored is all nonflammable and  noncombustible. It is estimated to cost over $200k to add sprinklers to the building.   Additionally, fertilizer mixed with fire suppression water could cause environmental  contamination and create issues with cleanup operations.