Owner / Applicant Information
Stephen D Jewell
Metropolitan School District of Warren Township
9150 EAST RAWLES AVENUE
INDIANAPOLIS IN 46229
Phone 3172137235
Email [email protected]
Submitter Information
Edwin L Rensink
RTM Consultants Inc
6640 Parkdale Place
Indianaplis IN  
Phone 3173297700
Email [email protected]
Project Information
Warren Central High School Pull Station Removal
9500 East 16th Street
Indianapolis IN 46229
County MARION
Project Type New   Addition   Alteration   Existing Y Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 3173275544 Email: [email protected]
Local Fire Official 
Phone: 3173275544 Email: [email protected]

Variance Details
Code Name: 12-4-9 Maintenance of Existing Buildings and Structures
Rule 4, Section 9(a), GAR
Conditions: Fire alarm manual pull stations will be removed from existing building areas that are fully  sprinklered, constructed in 1981, 1986, 1989, 1992, and 2002. The codes in effect when these  buildings were filed required manual pull stations.  Those codes were Official Regulation #7,  1985 IBC, 1989 IBC, and the 1998 IBC.

The building is classified as E Occupancy and Type IIB Construction.  The facility's original  building area dating to 1974 (with 2003 renovation) is partially sprinklered and is not included  in this variance request.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.  Sec. 907.2.3, exc. 3 of the 2014 Indiana Building Code permits fire alarm pull stations to be  omitted where the building is protected throughout with an automatic sprinkler system, and  notification appliances (horns and strobes) are activated by sprinkler water flow, and manual  activation is provided from a normally occupied location.

2.  The same exception was in Sec. 907.2.3 of the 2008 Indiana Building Code.  This exception is also included in the 2015 and 2018 editions of the International Building Code.

3.  The affected building areas are protected throughout with an automatic sprinkler system  which initiates the building fire alarm, as required.

4.  Means to manually activate the fire alarm system by Staff will be provided in the  administrative area.

5.  Based upon compliance with an exception in more recent codes, removal of manual pull  stations in the public areas of the building will not be adverse to life safety.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: Manual pull stations in the public areas of the building present a safety threat to students and  staff by allowing a convenient means for an intruder to initiate the building fire alarm system.