Owner / Applicant Information
Jane Hendrickson
River Centre, LLC
5205 ROBINSON ROAD
INDIANAPOLIS IN 46268
Phone 3177168042
Email JANE@BOXERGIRLLLC.COM
Submitter Information
Melissa  Tupper
RTM Consultants, Inc.
6640 Parkdale Place
Indianapolis IN  
Phone 3173297700
Email tupper@rtmconsultants.com
Designer Information
Frank E. Hindes
Cripe
3939 Priority Way S Drive
Indianapolis IN  
Phone 3177066324
Email fhindes@cripe.biz
Project Information
River Centre Apartments
E 2nd St
JASPER IN 47546
County DUBOIS
Project Type New   Addition Y Alteration   Existing   Change of Occupancy Y
Project Status F F=Filed U or Null=Unfiled
IDHS Issued Correction order?    
Violation Issued by: NA
Local Building Official
Phone: 3172321407 Email: cdeel@dhs.in.gov
Local Fire Official 
3172321407 Email: firechief@jasperindiana.gov
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IBC, 903.4
Conditions: The variance request is to not provide electronic monitoring of the post indicator valve.
    
The project involves the conversion of an and addition to an existing cabinet factory into a  mixed uses building with retail and restaurant on the 1st floor, apartments on the 2nd and 3rd  floor, and an occupied roof terrace. The overall building will be divided into 3 separate  buildings by 3-hour fire walls. Two of the buildings (Building A and C) are a change of use and  will be evaluated using Ch 34, the third building (Building B) is new construction between the  existing two buildings. Building B will contain A-2, M, and R-2 Occupancies. 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or we
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. The valve will be physically locked in the open position. 
2. The locking of valves in the correct position complies with the currently adopted 2010 edition of NFPA 13, Section 8.16.1.1.2. 
3. The local fire department is not opposed to the variance.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty) because  of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty) because  of major operational problems in the use of the building or structure.
Y
  Imposition of the rule would result in an undue hardship (unusual difficulty) because  of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an architecturally or a historically significant part of the building or structure.
 
Facts: The exterior electronics are in a very public, high traffic location that is vulnerable to tampering  and/or damage. The safest route is a chain and lock. The local fire authority supports this  approach.