Owner / Applicant Information
Mark  R Susemichel
Browning/Duke JV
6100 WEST 96TH STREET
INDIANAPOLIS IN 46278
Phone 3173447327
Email [email protected]
Submitter Information
Timothy  T Callas
J & T Consulting, LLC
8220
INDIANAPOLIS IN  
Phone 3178894300
Email [email protected]
Designer Information
Shawn M Curran
Curran Architecture
5719 Lawton Loop East Drive,
Indianapolis IN  
Phone 3172880681
Email [email protected]
Project Information
AllpointsMidwest Building 10
1705 Midwest Drive
Plainfield IN 00000
County HENDRICKS
Project Type New Y Addition   Alteration   Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 3178392561 Email: [email protected]
Local Fire Official 
3178392561 Email: [email protected]
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
2010 NFPA 72 26.6.3.2.1.4 (A)
Conditions: A new S-1 Occupancy warehouse facility of 495,000 square feet, Type IIB construction will  have two cellular communications on separate networks in lieu of two different transmission  technologies. Code requires a system employing DACT to have two lines of communication  with two different transmission technologies.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. The building will be protected with an automatic fire suppression system per NFPA 13, 2010  Edition.
2. Two separate cellular carriers will be utilized.
3. The system will check every 5 minutes-code allows test intervals of 24 hours.
4. Similar variances have been approved in the past for  this issue, but not limited to 6-12-03,  17-05-24, 17-05-38, 17-09-60 were approved with conditions that two separate cellular  carriers be utilized. 
5. The Plainfield Fire Department has been consulted (Chief Stevens) on this variance and are not opposed to the variance provided two separate cellular carriers will be utilized. 



 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: The owner's undue hardship involves the cost of providing two separate technologies while  cellular communication is the most reliable option and allows for faster notification of  transmission failures.