Owner / Applicant Information
Tim St. Clair
 
950 N MERIDIAN ST
INDIANAPOLIS IN 46204
Phone 8123539590
Email [email protected]
Submitter Information
Derek Holman
RTM Consultants, Inc.
6640 Parkdale Pl Suite J
Indianapolis IN  
Phone 3173297700
Email [email protected]
Designer Information
Alan Tucker
CSO Architects
8831 Keystone Crossing
Indianapolis IN  
Phone 3178487800
Email [email protected]
Project Information
IUH Bloomington Academic Health Center
SR46 and 14th Street
Bloomington IN 47408
County MONROE
Project Type New Y Addition   Alteration   Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order?    
Violation Issued by: NA
Local Building Official
Phone: 8123329763 Email: [email protected]
Local Fire Official 
8123329763 Email: [email protected]
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
2014 InBC Section 714.4.1.1.2
Conditions: T Ratings will not be provided at penetrations of horizontal assemblies that are not within a  wall cavity. 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. The building will be fully sprinklered.
2. Penetrating items will not be in contact with an combustible materials.
3. The project will comply with T Rating requirements of NFPA 101-2012 (enforced by CMS and ISDH on this project).
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
Y
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
  Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
Facts: Due to the limitations of T Rating assemblies, it is difficult to install T Rating assemblies in  many areas where they are required (at medical imaging equipment and electrical  panels/switchgears). T Ratings are meant to stop the transfer of heat from floor to floor. Since  there will be no combustibles in contact with the penetrating items, the risk of fire from heat  transfer is unlikely. 

Variance Details
Code Name:  Other Code (Not in the list provided)
2014 InBC Section 407.4.3.5.1
Conditions: A patient sleeping suite will be designed to not exceed 10,000 square feet. The InBC only  permits sleeping suites to be a maximum of 5,000 square feet. 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. Direct visibility from a constantly attended location will be provided.
2. A complete smoke detection system will be provided throughout the suite.
3. The building will be fully sprinklered.
4. The suite design will comply with the 2018 IBC and with NFPA 101-2012 (enforced on this  project by CMS and ISDH)
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: Due to the nature of the patient care in this area (NICU), it is the desire to maintain the space  as open as possible while maintaining certain security levels for the patients safety. The  design will meet the requirements of both the 2018 International Building and the requirements  of the Life Safety Code NFPA 101-2012.