Project Information
KAR Global Headquarters
11299 Illinois St.
CARMEL IN 46032
County HAMILTON
Project Type New Y Addition   Alteration   Existing   Change of Occupancy  
Project Status F F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 3175712444 Email: [email protected]
Local Fire Official 
3175712444 Email: [email protected]
Phone:

Variance Details
Code Name: 2014 IBC
1008.3.1, IBC
Conditions: The turnstiles installed at three (3) exterior exit locations on the 1st floor will not comply with  IBC requirements for revolving doors (mainly  collapsibility upon contact) - this is required for turnstiles more than 39 inches in height.  Actual height will be 62 inches - see attached cut  sheets.

The 5-story building includes office and assembly functions. 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.  The turnstiles will open upon fire alarm actuation.
2.  The turnstiles will fail open in the event of loss of power to the devices.  A battery back up  is provided in the event of loss of power to the building.  If power is not restored upon battery  exhaustion, the turnstiles will fully retract to permit free egress.
3.  The turnstiles permit two (2) 36-inch net clear openings at each of the exit locations,  exceeding required egress width.
4.  The two (2) enclosed stairs serving levels 2-5 have free egress to the exterior outside the  turnstile perimeter.
5.  The building is protected throughout with an automatic sprinkler system per NFPA 13.
6.  The proposed safeguards for the turnstiles exceed the minimum standards for revolving  doors used as a means of egress.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: The turnstiles are a necessary tool to restrict unwanted access to the building, and to  account for authorized personnel entering and leaving the building.