Owner / Applicant Information
Ryan Gallmeyer
NOS TBR, LLC
941 N MERIDIAN ST, INDIANAPOLI
INDIANAPOLIS IN 46204
Phone 3179741234
Email [email protected]
Submitter Information
Edwin Rensink
RTM Consultants Inc
6640 Parkdale Place
Indianaplis IN  
Phone 3173297700
Email [email protected]
Designer Information
SCOTT BARTEN PERKINS
BLACKLINE
1 N MERIDIAN ST
INDIANAPOLIS IN  
Phone 3178037900
Email [email protected]
Project Information
CityWay Phase 2 Building D
336 S Delaware St
INDIANAPOLIS IN 46204
County MARION
Project Type New Y Addition   Alteration   Existing   Change of Occupancy  
Project Status F F=Filed U or Null=Unfiled
IDHS Issued Correction order? No yes
Violation Issued by: LBD
Local Building Official
Phone: 3173275544 Email: [email protected]
Local Fire Official 
3173275544 Email: [email protected]
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
714.4.1.2, 2014 IBC
Conditions: The double top plate of nonrated interior partitions interrupts the fire-rated ceiling membrane  of 1-hour floor-ceiling and roof-ceiling assemblies in the Type VA building.  Based upon  language in the adopted version of the International Building Code, this condition is only  permitted where the interior partitions are 1-hour fire-rated.
The project involves construction of 4-story Type VA buildings over a 1-story Type IA podium consisting of 1st floor commercial tenant spaces and attached open parking garage. The  project will employ the horizontal building separation ¿podium¿ option per Sec. 510.2, with 1st floor of Type IA Construction, and the top 4 floors designed as Type VA Construction. 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.    The 2015 and 2018 Editions of the International Building Code permit the rated ceiling  membrane to be interrupted by the double top plate of an interior partition sheathed with Type  X gypsum board.  The construction complies with this provision.
2.   Identical variances have been approved previously, including 19-06-27b, 19-02-27, 17- 08-41g, and 18-12-16.
3.    The Type VA building is protected with an automatic sprinkler system per NFPA 13R.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
 
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: Conventional wood frame construction involves framing of interior walls prior to installation of  the gypsum ceilings.  The change made in the 2015 International Building Code recognized  this condition and deemed it to not be adverse to safety. The project framing is currently  constructed. 

Variance Details
Code Name:  Other Code (Not in the list provided)
714.4.1.3, 2014 IBC
Conditions: Bathroom exhaust ducts which penetrate the double top plate of floor-ceiling and roof-ceiling assemblies transition from hard duct to flex duct after passing through the top plate.  Based  upon the flex ducts being of combustible construction, the transition described is not  permitted.
The project involves construction of 4-story Type VA buildings over a 1-story Type IA podium consisting of 1st floor commercial tenant spaces and attached open parking garage. The  project will employ the horizontal building separation ¿podium¿ option per Sec. 510.2, with 1st floor of Type IA Construction, and the top 4 floors designed as Type VA Construction. 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.    The flex duct is a Class I air duct in compliance with UL 181, and has a maximum flame  spread rating of 25.
2.   The rigid steel duct extends approximately 2 feet above the double top plate penetration.   The transition occurs well above the point of penetration into the assembly and will not  adversely impact the fire rating of the assembly.  
3.   The flex duct will not adversely affect the fire rating of the assembly, as the fire test per  ASTM E-119 for a horizontal assembly tests for fire from the room below the assembly.  In  order to enter the cavity of the assembly, a fire would have to penetrate the gypsum board  covering the wall assembly and burn through the double top plate.  The duct penetration of  the top plate will be firestopped as required for a membrane penetration.
4. The Type VA building is protected with an automatic sprinkler system per NFPA 13R.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: The use of flex duct in the horizontal cavities allows for more secure joints than rigid duct, and permits navigation through the cavity.