Project Information
Convergence
101 Foundry Dr
WEST LAFAYETTE IN 47906
County TIPPECANOE
Project Type New Y Addition   Alteration   Existing   Change of Occupancy  
Project Status F F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 7657755130 Email: [email protected]
Local Fire Official 
7657755130 Email: [email protected]
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
2014 InBC 905.4
Conditions: New five (5) story office building will have standpipe outlets located at main floor landings for  enclosed exit stair and at elevator lobby area for the open stair.  Code requires the outlets to  be located on the intermediate floor landing.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.  As required  by code, the building is sprinklered per NFPA 13.
2.  2018 and 2021 editions of IBC require the outlets to be on the main landings. They also  allow location in open corridor for open exit access stairs.
3.  2013, 2016 and 2019 editions of NFPA 14 have a basic requirement to locate the outlets on  the main landing.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
  Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
Facts: Later / more recent codes require the standpipe outlets to be located on the main floor  landings.