Owner / Applicant Information
Jason Fee
Schneck Medical Center
411 W TIPTON STREET
SEYMOUR IN 47274
Phone 8125220120
Email [email protected]
Submitter Information
Derek Holman
RTM Consultants, Inc.
6640 Parkdale Pl Suite J
Indianapolis IN  
Phone 3173297700
Email [email protected]
Designer Information
Brian Mader
arcDESIGN
201 n delaware
Indianapolis IN  
Phone 3179519192
Email [email protected]
Project Information
Schneck Pharmacy Expansion
411 W Tipton St
SEYMOUR IN 47274
County JACKSON
Project Type New   Addition   Alteration Y Existing   Change of Occupancy  
Project Status F F=Filed U or Null=Unfiled
IDHS Issued Correction order?    
Violation Issued by: NA
Local Building Official
Phone: 8125223423 Email: [email protected]
Local Fire Official 
8125223423 Email: [email protected]
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
2014 InBC 717.6.1
Conditions: Ductwork penetrating 1 floor assembly in an I-2 Occupancy will not be provided with a shaft  enclosure. Code requires ductwork that penetrates floor assemblies in an I-2 Occupancy  are required to be within a shaft enclosure
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. A fire damper will be provided at the floor level where ductwork penetrates the floor  assembly.
2. The building is fully sprinklered.
3. The design complies with Section 5.3.2 of NFPA 90A - 2012 Standard for Installation of HVAC  Systems, as required by CMS and ISDH.
4. Similar variances have been granted in the past on other healthcare facilities (17-06-14,  17-08-59, 18-02-04 and 18-08-29)
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
Y
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: The hardship is the cost and physical limitations of the existing facility to provide a shaft  assembly, and additional fire dampers at the shaft enclosures. The design, without a shaft  enclosure, complies with the Life Safety Code as required by CMS and ISDH.