Owner / Applicant Information
Jade Schuckman
Medicine Plus Pharmacy
2412 16TH STREET
BEDFORD IN 47421
Phone 8122753383
Email [email protected]
Submitter Information
Carrie  Ballinger
RTM Consultants, Inc.
6640 Parkdale Place, Ste J
Indianapolis IN  
Phone 3173297700
Email [email protected]
Designer Information
Bryan Imhoff
Imhoff Engineering, Inc.
631 X Street
Bedford IN  
Phone 8122753906
Email [email protected]
Project Information
Medicine Plus Pharmacy
2412 16th St
BEDFORD IN 47421
County LAWRENCE
Project Type New Y Addition   Alteration   Existing   Change of Occupancy  
Project Status F F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 8122751631 Email: [email protected]
Local Fire Official 
8122751631 Email: [email protected]
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IBC Sec. 903.2.11.1
Conditions: Code requires sprinklers to be provided in stories without openings (for fire department  access) with over 1,500 square feet of floor area.   The request is to not provide sprinklers in  the basement level of a new pharmacy building.  

The project involves construction of a new 1-story plus basement pharmacy building with  approximately 3,000sf per floor. The building is classified Type VB construction with B/M/F- 2/S-1 occupancies. 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. The building will be provided with a monitored fire alarm system  (not required by code). 
2. An exterior door is provided at the top of the open interior stairway.
3. Distance to the opposite basement wall from the bottom of the stairs is less than 50 feet  (approx. 45 feet).  Travel down the stairs from the exterior door at 1st floor is approximately 30  feet. (Code would permit exterior opening on one side of basement with opposite wall less  than 75 feet without sprinklers.)
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
Y
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
 
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
  Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
Facts: Due to the limited space on the site, with pharmacy drive-through directly adjacent to the  building on two sides and parking on the other two sides, there is not enough room to provide an exterior opening from the basement level.