Owner / Applicant Information
Jim Mullins
Tipton County
101 E. JEFFERSON STREET
TIPTON IN 46072
Phone 7656752794
Email [email protected]
Submitter Information
Carrie Ballinger
RTM Consultants, Inc.
6640 Parkdale Place, Ste J
Indianapolis IN  
Phone 3173297700
Email [email protected]
Designer Information
Joseph Mrak
Securitecture
7381 E 209th St
Noblesville IN  
Phone 3176956725
Email [email protected]
Project Information
Tipton County Jail
2300 W Indiana SR 28
TIPTON IN 46072
County TIPTON
Project Type New Y Addition   Alteration   Existing   Change of Occupancy  
Project Status F F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 7656756063 Email: [email protected]
Local Fire Official 
7656756063 Email: [email protected]
Phone:

Variance Details
Code Name: 2010 NFPA 13 Installation of Sprinkler Systems (675 IAC 28-1-5)
Sec. 8.5.5.3.1
Conditions: A 4'-7" wide mezzanine obstruction will not be provided with sprinklers below.  Code requires sprinklers to be installed under obstructions over 4 feet wide.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: The mezzanine is noncombustible with open grating. The mezzanine is only used for walkway access to mezzanine cells. There will be no storage on the mezzanine to obstruct the open  grating.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: Exposed water pipe and sprinkler heads below the mezzanine would be subject to vandalism  and portions of damaged equipment potentially used as weapons by the inmates.