Project Information
Install 17 new HVLS Fans
5349 W 76th Street
Indianapolis IN 46268
County MARION
Project Type New   Addition   Alteration Y Existing   Change of Occupancy  
Project Status F F=Filed U or Null=Unfiled
IDHS Issued Correction order? yes yes
Violation Issued by: LFD
Local Building Official
Phone: 3173475860 Email: [email protected]
Local Fire Official 
Phone: 3173475860 Email: [email protected]

Variance Details
Code Name: NFPA 13 - 2010
8.6.5.2.1.10
Conditions: Fans over 60 inches are in violation as a sprinkler obstruction.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: A shunt trip has been installed to fire alarm to shut down fans if fire alarm is activated in  accordance with NFPA 13 Section 8.6.5.2.1.10.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
 
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: Inspector Comments:  Fans over 60 inches are in violation as a sprinkler obstruction. Need to  file a variance
using above NFPA 13 Section 8.6.5.2.1.10 indicating a shunt trip has been installed to fire  alarm to shut down
fans if fire alarm is activated.