Owner / Applicant Information
David Byers
Tippecanoe County Commissioner
20 NORTH THIRD STREET
LAFAYETTE IN 47901
Phone 7654239215
Email [email protected]
Submitter Information
Dennis Bradshaw
Fire Protection & Code Consultants, LLC
1520 Main Street
Indianapolis IN  
Phone 3174865188
Email [email protected]
Designer Information
Nick Davis
Browning Day Mullins Dierdorf
626 North Illinois Street
Indianapolis IN  
Phone 3176355030
Email [email protected]
Project Information
Tippecanoe County Fairground Improvements Project Phases 2,3
1406 Teal Road
Lafayette IN 47905
County TIPPECANOE
Project Type New Y Addition   Alteration   Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 7658071000 Email: [email protected]
Local Fire Official 
7658071000 Email: [email protected]
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
602.1 and Table 601, 2014 IBC
Conditions: A new sprinklered coliseum building of Type I-B construction will have a portion of it's non- rated roof structure located less than 20 feet (14 feet) above the floor below and will have  exposed steel columns. The code requires the entire roof structure to be not less than 20  feet above the floor below to permit a non-rated structure. The code requires the columns to  be protected with a one-hour fire resistance rating.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. The building will be protected by an automatic fire sprinkler system designed per NFPA 13,  2010 Edition.
2. The sprinkler density and spacing in the areas where the roof is less than 20 feet above the floor will have it's density and spacing increased from Ordinary Hazard Group 1 to Ordinary  Hazard Group 2.
3. The exposed steel columns will be protected by additional sprinkler heads located at the  columns designed to protect the columns.
4. Similar variances have been granted for other projects.
 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
 
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: The owner's undue hardship is the cost to provide and maintain fireproofing on the exposed  steel roof structure and the exposed steel columns.