Owner / Applicant Information
Tim St. Clair
RTM Consultants, Inc.
950 N MERIDIAN ST
INDIANAPOLIS IN 46204
Phone 8123539590
Email [email protected]
Submitter Information
Derek Holman
RTM Consultants, Inc.
6640 Parkdale Pl Suite J
Indianapolis IN  
Phone 3173297700
Email [email protected]
Designer Information
Alan Tucker
CSO Architects
8831 Keystone Crossing
Indianapolis IN  
Phone 3178487800
Email [email protected]
Project Information
IUH Bloomington Academic Health Center
SR46 and 14th Street
Bloomington IN  
County MONROE
Project Type New Y Addition   Alteration   Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order?    
Violation Issued by: NA
Local Building Official
Phone: 8123329763 Email: [email protected]
Local Fire Official 
8123329763 Email: [email protected]
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
2014 InBC Section 1018.4
Conditions: Dead end corridors will be designed to a maximum length of 30'. The IBC only permits a  maximum dead end corridor in I-2 Occupancies of 20'. Section 18.2.5.2 of NFPA 101-2012  permits dead end corridors in Healthcare Occupancies to be a maximum of 30'.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. Section 18.2.5.2 of NFPA 101-2012 permits dead end corridors in Healthcare Occupancies  up to 30' in length. (Enforced on the project by ISDH and CMS)
2. Similar variances have been granted in the past on other Healthcare facilities. (18-05-23,  19-02-20)
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
Y
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
 
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: In order to create dead end corridors no more than 20' in length would require a re-design in  portions of the hospital layout. The project is in final stages of design and a re-design for  these areas would cause a delay in the project.