Project Information
New Northside Elementary School
10701 Petersburg Road
Evansville IN 47725
County VANDERBURGH
Project Type New Y Addition   Alteration   Existing   Change of Occupancy  
Project Status F F=Filed U or Null=Unfiled
IDHS Issued Correction order? yes yes
Violation Issued by: SBC
Local Building Official
Phone: 8124367885 Email: [email protected]
Local Fire Official 
8124367885 Email: [email protected]
Phone:


Variance Details
Code Name: 2009 Indiana Electrical Code (675 IAC 17-1.8)
300.10
Conditions: Nature of Non-Compliance

The method of installation used is based upon the interpretation of NEC 300.10 by IBEW  electricians in that the raceways inside the masonry wall meet Exception 1 to NEC 300.10.   The short sections of raceway inside the masonry walls enter a wall mounted box and both  are secured by the wall rather than an electrical box connector.  

The installation method used is a common practice and has long been accepted by the  Evansville Vanderburgh County Building Commission (Local Building Commission).  On this  project alone, the Local Building Commission inspected and approved the connection  method in question on seven occasions and passed the installation on each inspection.   Ultimately the Local Building Commission issued a final inspection on the electric system with no conditions to acceptance.  

After construction of the Project was complete, the installation method was brought to the  Indiana State Division of Fire Protection and Building Safety (DHS).  DHS issued an  interpretation of NEC 300.10, opining that the installation did not meet the exception and is  non-compliant.


 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: See uploaded document - Not adverse to HSW.

 ALVA is an electrical contractor specializing in commercial electrical construction.  ALVA  employs, on average, 100 electricians and its employment accounts for over 10% of the IBEW  Local 16 employment.  
 ALVA relies exclusively upon IBEW-trained electricians trained by the Joint Apprenticeship  Training Committee.  The IBEW, NECA, and the JATC partner to provide the most highly trained  electrical workforce possible.  IBEW electricians are trained to follow the NEC, which is the  Indiana Electric Code.  
 The conduit installation method in question has been commonly used where a ground fault  conductor is used and bonded to equipment boxes, and has been used by IBEW electricians in Southern Indiana for many years.  The method in question has continuously been  accepted by the Vanderburgh County Building Commission and the State Fire and Building  Safety Division.  Vanderburgh County and other Indiana County buildings contain identical  installations including many EVSC buildings.
 The building, and installation in question, was regularly inspected and approved during  construction through County and State inspections.  Vanderburgh County inspected  installations of the type that are now in violation repeatedly and passed the installations as it  always has.  Vanderburgh County issued seven partial rough-in approvals for the installation, a final Green Tag approval of the electric system, and approved the building for occupancy.  
 Connections were not hidden from inspectors, and the connections were known to be a  common IBEW practice.  The connections to the pipes in masonry walls were not considered  adverse to health, safety, nor welfare during prior years of acceptance and were considered  code compliant until July of 2018.
 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 

Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
  Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
Facts: Facts demonstrating imposition of the rule would result in undue hardship because of  excessive costs of additional and altered construction elements.

ALVA Electric Inc. (żALVAż) is under contract to construct the electrical system for the building in accordance with code authority mandates.  The violation in this case concerns conduits  that are a part of a completed structure and the conduits in question are now encased in  solid concrete walls.  All other building systems are complete and share above roof space  with the electrical system components.  

In order to gain the access needed to change the conduit connections, a large part of the  building systems will have to be demolished.  Workers will need access that allows for  disassembly of the conduit system and to perform partial demolition of the concrete masonry  walls.  The cost of changing the conduit system has not been fully estimated, but would likely  be more than a million dollars and would take years.  

Imposition of the Rule will result in undue hardship to the Vanderburgh County School  Corporation as well as ALVA because of major operational problems in the use of the building  or structure.  Attempting to perform partial demolitions of the building, electrical system  changes, and rebuilding portions of the building over the summers is impractical and will  result in portions of the school being unusable or closings of the entire school.  The time that  changing the electrical system will take and the operational problems will drive the costs of  imposition of the rule to an unknown amount of money that ALVA does not possess.