Owner / Applicant Information
KATHY DILLON
TOWN OF BROWNSBURG
61 NORTH GREEN STREET
BROWNSBURG IN 46112
Phone 3178521114
Email [email protected]
Submitter Information
JEREMY NITKA
 
150 WEST MARKET ST
INDIANAPOLIS IN  
Phone 3172362845
Email [email protected]
Designer Information
MATT PALTE
ARCADIS
100 E Campus View Blvd
COLUMBUS OH  
Phone 6149859275
Email [email protected]
Project Information
BROWNSBURG WWTP EXPANSION
225 Mardale Dr
BROWNSBURG IN 46112
County HENDRICKS
Project Type New Y Addition   Alteration   Existing   Change of Occupancy  
Project Status F F=Filed U or Null=Unfiled
IDHS Issued Correction order?    
Violation Issued by: NA
Local Building Official
Phone: 3178521128 Email: [email protected]
Local Fire Official 
3178521128 Email: [email protected]
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IBC, 903.2.5
Conditions: Sprinkling system will not be provided in a Phosphorus Removal Building. Phosphorus  Removal Building stores Aluminum Sulfate, a corrosive liquid per DOTn 49 CFR Part 173.137,  which is used by the wastewater treatment facility. Since amount of stored quantity exceeds  the maximum allowable quantity of material posing a hazard, building is classified with an H- 4 Occupancy.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. Aluminum Sulfate is not a flammable or combustible liquid. The building is classified as a H- 4 occupancy because Aluminum Sulfate is listed as a corrosive.
2. The building is normally not occupied and can only be occupied by authorized personal  who have been trained for this type of hazard.  Building houses 1 aluminum sulfate storage  tank with feed pumps.
3. The building is constructed with noncombustible materials and is equipped with a fire  extinguisher at each exit.
4. Secondary containment is provided for the tank.
5. The room will not be used to store combustible materials.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
 
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: The hardship is the cost of installing and maintaining an automatic sprinkler protection in a  building without a fire hazard. In this case, the sprinkler system would not add any benefit to  safety.