Owner / Applicant Information
Chip Mehaffey
Loogootee Community Schools
201 BROOKS AVENUE
LOOGOOTEE IN 47553
Phone 8122952595
Email [email protected]
Submitter Information
Dennis Bradshaw
Fire Protection & Code Consultants, LLC
1520 Main Street
Indianapolis IN  
Phone 3174865188
Email [email protected]
Designer Information
Josh Heinz
Myszak + Palmer Architects
903 Broadway Street
Vincennes IN  
Phone 8128860350
Email [email protected]
Project Information
Loogootee Community Schools Renovations - Elementary School
101 Costtello Drive
Loogootee IN 47553
County MARTIN
Project Type New   Addition Y Alteration Y Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 3174176650 Email: [email protected]
Local Fire Official 
3174176650 Email: [email protected]
Phone:

Variance Details
Code Name: 12-4-12 Existing Buildings; Additions or Alterations
Section 12 (f)
Conditions: An existing non-sprinklered school of 29,584 square feet on the first floor constructed of Type II-B construction will have an existing 339 square feet entry canopy renovated and enclosed  as a new security vestibule. The new vestibule and existing building will exceed the  allowable area permitted for Type II-B construction.The code would require the vestibule to  be separated from the existing school by a 4 hour fire wall.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. The new vestibule will be constructed of non-combustible Type II-B construction.
2. The existing smoke detection system will be extended into the new vestibule.
3. The fire load of the vestibule will be extremely low.
4. The vestibule is need to provide additional security and safety for the students and staff.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: The owner's undue hardship is the need to provide a security vestibule for the school without  the hardship and cost of providing a structurally independent 4 hour fire wall to separate the  vestibule from the existing school.