Owner / Applicant Information
P.K. Patel
Indiana University
1800 NORTH RANGE ROAD
BLOOMINGTON IN 47408
Phone 8128557894
Email [email protected]
Submitter Information
Ralph  Gerdes
Ralph Gerdes Consultants, LLC
5510 S. East St.
Indianapolis IN  
Phone 3177873750
Email [email protected]
Designer Information
Alan Tucker
CSO Architects
8831 Keystone Crossing
Indianapolis IN  
Phone 3178487800
Email [email protected]
Project Information
IU McNutt Dining Addition & Renovation
1101 N Fee Lane
Bloomington IN 47406
County MONROE
Project Type New   Addition Y Alteration Y Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 8123492967 Email: [email protected]
Local Fire Official 
8123492967 Email: [email protected]
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
2014 InBC, 508.4
Conditions: Addition Groups A-2/M occupancy will not have occupancy separation from remainder of the building (A-2, S-1, S-2, R-2,and B occupancy).  Mixed occupancy building with open stairs  and one (1) hour structure will not have fire ratings for separated uses.  Code requires some two (2) hour separations in nonsprinklered building.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: Ground Floor and First Floor will be sprinklered per NFPA 13.

 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: Cost of providing fire barriers or sprinklering entire building is the hardship.

Variance Details
Code Name:  Other Code (Not in the list provided)
2014 InBC, 903.2.1.2
Conditions: Two (2) story addition of approx 22,423 sq.ft. increases existing fire area,requiring entire  building to be sprinklered.  The partial third and fourth floor areas will not be sprinklered.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.  The Ground Floor and First Floor will be sprinklered per NFPA 13.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
  Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
Facts: Cost of sprinklering upper floors, where no work is planned, is the hardship.
Variance Details
Code Name: 12-4-12 Existing Buildings; Additions or Alterations
12(f)(3)
Conditions: Existing four (4) story dining, classroom, apartment and storage building will have an addition on the first two (2) levels of the building.  Ground Floor addition will be approx 12,000 sq.ft.  and First Floor will be approx 11,000 sq.ft.  The additons will bring the building into  noncompliance with current allowable floor area and height for a non-sprinklered building.  First floor will be approx 39,000 sq.ft. with 16,625 sq.ft. permitted for Type IIA (1 hour)
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.  First two (2) floor levels will be sprinklered per NFPA 13.
2.  Addition will match existing Type IIA (1 hour) construction.

 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:

Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: Cost of sprinklering entire building or upgrading existing construction is the hardship.
Variance Details
Code Name:  Other Code (Not in the list provided)
2014 InBC, Table 1018.1
Conditions: Ground Floor will not have one (1) hour fire rated corridors.  Code requires one (1) hour  corridors in buildings that are not fully sprinklered.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.  Ground Floor and First Floor will be sprinklered per NFPA 13.
2.  New exit passageway will be one (1) hour.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: cost of providing upgraded corridor construction on floor that will be sprinklered is the  hardship.