Owner / Applicant Information
Greg Graham
Ball State University
3401 NORTH TILLOTSON AVE.
MUNCIE IN 47306
Phone 7652852828
Email [email protected]
Submitter Information
Ralph Gerdes
Ralph Gerdes Consultants, LLC
5510 S. East St.
Indianapolis IN  
Phone 3177873750
Email [email protected]
Designer Information
Alan Tucker
CSO Architects
8831 Keystone Crossing
Indianapolis IN  
Phone 3178487800
Email [email protected]
Project Information
BSU North Residential Neighborhood Phase #2
1701 West McKinley Avenue
Muncie IN 47306
County DELAWARE
Project Type New Y Addition   Alteration   Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 3172330307 Email: [email protected]
Local Fire Official 
3172330307 Email: [email protected]
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
2014 InBC, 707.5.1
Conditions: Two (2) hour shafts for ducts and piping will be supported by non-rated (0 Hour) floor in  Type IIB buildings.  Code requires shafts to be supported by two (2) hour floor.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.  Building will be sprinklered per NFPA 13, as required by code.
2.  Code allows one (1) shafts to be supported by non-rated floors in Type IIB construction.
3.  Exit stairs and elevators will be in self-supporting shafts.
4.  For 70 years Indiana codes did not require fire-rated supported construction.  There has  not been a problem.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: Cost to upgrade a portion of the floor assembly is the hardship.

Variance Details
Code Name:  Other Code (Not in the list provided)
2014 InBC, 1018.6
Conditions: New college dormitory will have lounges / kitchnettes open to the corridor.  Code requires  0.5 hour wall to separate rooms from the corridor.
 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.  Building will be sprinklered per NFPA 13, as required by code.
2.  NISTIR 7120 fire tests on open dormitory day rooms shows sprinklers will control a fire. limit smoke generation to maintain tenable conditions in the corridor.
3.  Based on these tests, NFPA 5000 - 2018, 24.3.6.4 and NFPA 101-2018, 28.3.6.3.2 allow such rooms to be open to the corridor.
4.  Numerous variances approved for lounges.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: Open lounges are intended to create collegial atmosphere within the dormitory.
Variance Details
Code Name:  Other Code (Not in the list provided)
2014 InBC, 1009.3
Conditions: New five (5) story college dormitory will have an open stairs for five (5) stories.  Code limits  open exit access stairways in R occupancies to four (4) stories.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.  Building will be sprinklered per NFPA 13, as required by code.
2.  Stairs will have twelve (12) inch draft curtain and close spaced sprinklers around the floor  openings.
3.  Open stairs are not required for exiting.  Each wing will have two (2) enclosed exit stairs.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 

Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
  Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
Facts: University wants to encourage use of stairs and open stairs will assist in collegial  atmosphere.
Variance Details
Code Name:  Other Code (Not in the list provided)
2014 InBC, 905.4
Conditions: New five (5) story dormitory will have standpipe hose outlets on the main floor landings.   Code requires hose outlets on the intermediate floor landings.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.  NFPA 14 - 2016 Edition, Section 7.3.2.1 allows the hose outlets to be on the main floor  landings.
 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
 
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: Location at intermediate floor landing results in increased costs.

Variance Details
Code Name:  Other Code (Not in the list provided)
2014 InBC, 716.5.3.1
Conditions: New dormitory will not have corridor door smoke and draft control assemblies (gaskets).   The code requires 20 minute corridor doors to have gaskets.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.  Building will be sprinklered per NFPA 13, as required by code.
2.  NIST TN 1658 documents sprinkler fire tests that show dormitory room doors can remain  open during a fire and the corridor tenability is maintains.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: Students tend to prop open room doors, negating the smoke gaskets.
Variance Details
Code Name:  Other Code (Not in the list provided)
2014 InBC, 716.5.9
Conditions: Door closers will not be provided on 20 minute corridor doors.  Code requires fire rated  doors to be self-closing.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.  Building will be sprinklered per NFPA 13, as required by code.
2.  NIST TN 1658 documents sprinkler fire tests which show dormitory rooms with open doors  will not affect corridor tenability.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 

Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: Students tend to prop open doors, overcoming the closer.  Cost of closers is not justified  when fire tests show they are not required to maintain corridor tenability.