Owner / Applicant Information
Jon Eller
Goodwill of Central and Southern Indiana
1635 WEST MICHIGAN STREET
INDIANAPOLIS IN 46222
Phone 3175244247
Email [email protected]
Submitter Information
Timothy Callas
J & T Consulting
8220
INDIANAPOLIS IN  
Phone 3174464389
Email [email protected]
Designer Information
Shawn Curran
Curran Architecture
5719 Lawton Loop East Drive,
Indianapolis IN  
Phone 3172880681
Email [email protected]
Project Information
Goodwill Clarksville Outlet
1212 Applegate Lane
Clarksville IN 00000
County CLARK
Project Type New   Addition Y Alteration   Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 8122831510 Email: [email protected]
Local Fire Official 
8122831510 Email: [email protected]
Phone:


Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IBC Table 503/507.3
Conditions: An S-1 Occupancy, Type IIB construction addition of 70,200 sf to the existing M/S-1  Occupancy, Type IIB construction building of 39,970 sf will have south exterior wall (225 lineal feet) less (47 feet to property line) than the required 60 feet from property line for unlimited  area. Code requires the building to have 60 feet of frontage or a 4-hour fire wall. All other  portions of exterior walls have a minimum of 60 feet of frontage. Refer to drawing for location.  The exterior walls will be precast tilt up walls that have been tested for 2-hour fire resistance.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. The existing building and addition is and will be protected with an automatic fire  suppression system per NFPA 13, 2010  
    Edition. The existing building sprinkler system was designed to NFPA 13. 
2. The South exterior wall will be provided with close spaces sprinklers a maximum 6'-0" on  center for the full length (225 feet) of 
    the wall.  The close spaced sprinklers will be a water curtain design per Section 11.3.3  NFPA 13, which requires the system to 
    be hydraulically designed to provide 3 gallons per minute per lineal foot of water curtain,  with no sprinklers discharging less 
    than 15 GPM.
3. Previous variances have been approved for this issue 14-05-43, 18-07-69 and many  others. 

 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
 
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: The owner's undue hardship involves the cost to upgrade the precast exterior wall ($ 160,000  +) to four (4) hour fire wall.