Owner / Applicant Information
Richard Miller
Indiana American Water - Richmond
153 NORTH EMERSON AVENUE
GREENWOOD IN 46143
Phone 3178852439
Email [email protected]
Submitter Information
Christina RTM Consultants Collester
RTM Consultants
6640 Parkdale Place
Indianapolis IN  
Phone 3173297700
Email [email protected]
Designer Information
Zheng-Ming Wang
Hazen and Sawyer
4011 WestChase Blvd
Raleigh NC  
Phone 9197558568
Email [email protected]
Project Information
Middle Fork WTP Improvements
1730 Sylvan Nook Drive
RICHMOND IN 47374
County WAYNE
Project Type New Y Addition   Alteration   Existing   Change of Occupancy  
Project Status F F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 7659837268 Email: [email protected]
Local Fire Official 
7659837268 Email: [email protected]
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IBC  903.2.5.1 
Conditions: Sprinklers will not be provided in a water treatment building classified as a B, F-2 and H-4  Occupancy. Buildings that exceed the maximum allowable quantity of materials that are  health hazards are classified as an H-4 Occupancy. The building will store Sodium  Hypochlorite, Sodium Hydroxide, Ferric chloride, Sodium permanganate, Hydrofluosilicic  acid and other toxic/corrosive liquid as attached, which are used in the water treatment  process at the facility. 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: The two story building  is Type II-B construction. The H-4 occupancy occurs in a portion of  the building that is a single story.  The area of the building does not exceed the non-The  chemical rooms are separated from the remainder of the structure by 3 hr fire  walls.sprinklered allowable area for  the F-2 and B occupancies. 

The chemicals are non-combustible.  No combustibles are stored in the H-4 occupancy. 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
Y
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: The hardship is the cost of installing and maintaining an automatic sprinkler protection in a  building without a fire hazard. The Indiana deleted exception 4  to section 903.3.1.1.1  in the  model code would permit the elimination of the sprinkler systems for these non-combustible  rooms. In this case, the sprinkler system would not add any benefit to safety.