Owner / Applicant Information
John C Hart
500 Mass, LLC
805 CITY CENTER DRIVE
SUITE 120
CARMEL IN 46032
Phone 3175734800
Email [email protected]
Submitter Information
Edwin   Rensink
RTM Consultants Inc
6640 Parkdale Place
Suite J
Indianapolis IN  
Phone 3173297700
Email [email protected]
Designer Information
Sarah S Hempstead
Schmidt Associates
415 Massachusetts Avenue
 
Indianapolis IN  
Phone 3172636226
Email [email protected]
Project Information
Penrose on Mass
502 Massachusetts Avenue
 
Indianapolis IN 46204
County MARION
Project Type New Y Addition   Alteration   Existing   Change of Occupancy  
Project Status F F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 3173275544 Email: [email protected]
Local Fire Official 
3173275544 Email: [email protected]
Phone:


Variance Details
Code Name:  Other Code (Not in the list provided)
714.3, 2014 IBC
Conditions: LVL (laminated veneer lumber) beams penetrate the gypsum board membranes of 2-hour fire walls in a number of locations.  There is no available listed fire stop system or 2-hour wall  test specifically validating this type of penetration.
The project involves construction of a mixed use development that includes a Type IA podium consisting of two (2) levels of below-grade parking and 1st floor commercial tenant spaces,  and 4 stories + mezzanines Type VA residential apartments.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.   The LVL¿s approach heavy timber mass - they are typically 3½¿ X 12" in size.   The beams tie into wood ¿posts¿ within the 2-hour wall assembly consisting of three (3) 2" X 6" nominal  studs fastened together.  The large mass of the members involved have an inherent fire- resistance.
2. The opening through the gypsum board membrane will be firestopped around the beam  penetrations with fire caulking.
Small closets will be provided with sprinkler protection (not required for a 13R system).
3.   The building is protected by an NFPA 13R sprinkler system, with enhancements including  a design density of 0.1 gpm per sq ft per NFPA 13 in lieu of 0.05 gpm per sq ft permitted per  NFPA 13R, design area per NFPA 13 in lieu of the reductions in design area permitted per  NFPA 13R, and floor control valves will provided to permit annunciation of individual floors.
4.   Based upon the mass of the penetrating structural members involved and enhanced  sprinkler protection, the penetrations of the 2-hour wall will not be adverse to safety.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: Imposition of the rule at this point in construction would require significant re-design and re- construction of portions of the as-built construction.