Owner / Applicant Information
William L Nisley
L R Nisley & Sons
62724 CR 35
GOSHEN IN 46528
Phone 5746424267
Email [email protected]
Submitter Information
Timothy   Callas
J & T Consulting, LLC
8220 Rob Lane
Indianapolis IN  
Phone 3178894300
Email [email protected]
Designer Information
Douglas L Graham
Barr Design Group, LLC
502 South Main Street
Goshen IN  
Phone 5745346531
Email [email protected]
Project Information
L R Nisley & Sons Building
62724 CR 35
Goshen IN 46528
County ELKHART
Project Type New Y Addition   Alteration   Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 5749714678 Email: [email protected]
Local Fire Official 
5749714678 Email: [email protected]
Phone:


Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IBC 903.2.4.1
Conditions: A new F-1 Occupancy wood working facility of 18,496 sf, of Type VB construction will not be  provided with an automatic fire suppression system. Code requires woodworking operations  containing a fire area in excess of 2,500 square feet to be provided with an automatic fire  suppression system.  The building will be provided with a 3-hour fire wall so the total fire  area for each compartment will be less than 12,000 sf for compliance with Section 903.2.9  and allowable area per Section 503.1. 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. The facility will be provided with a duct collection system that will prevent the release of  ¿finely divided combustible waste or use of finely divided combustible materials. The dust  collection system will be designed and installed per NFPA 664, 2012  Edition that includes  exterior silo with collection manifold with individual connections to each cutting and sanding  machine.  
2. The dust collection system will immediately evacuate the finely divided combustible waste  from the building to exterior silo    mitigating potential for risk of fire and/or explosion, thus  variance is not adverse to the safety of the occupants. 
3. Previous variances have been approved for this issue 15-01-16, 14-05-7, 11-10-16, 11-10- 17, 12-06-4 ,15-08-47,Variance ID 16345, 16-10-31, 17-10-09, 17-11-12, 18-03-62 and most  recent for J & T Consulting 18-06-23.
 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
 
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: The owner's undue hardship involves the cost ($175,000 +) to provide a fire suppression  system in this rural area. There is no city or public water supply and there are no plans in the future for such water supply. Subdividing the building into 2,500 square feet fire areas is not  feasible as it would not be practical for the manufacturing process.