Owner / Applicant Information
David L Cooper
Community Reinvestment Foundation (CRF Affordable Housing, Inc.)
44 NORTH GIRLS SCHOOL ROAD
INDIANAPOLIS IN 46214
Phone 3175542100
Email [email protected]
Submitter Information
Melissa   Tupper
RTM Consultants, Inc.
6640 Parkdale Place
Indianapolis IN  
Phone 3173297700
Email [email protected]
Designer Information
Robert   Bray
American Structurepoint, Inc.
7260 Shadeland Station
Indianapolis IN  
Phone 3175475580
Email [email protected]
Project Information
Glasswater Creek of Plainfield
10480 Glasswater Lane
Plainfield IN  
County HENDRICKS
Project Type New Y Addition   Alteration   Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order?    
Violation Issued by: NA
Local Building Official
Phone: 3178392561 Email: [email protected]
Local Fire Official 
3178392561 Email: [email protected]
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IBC, 1018.1
Conditions: The wall enclosing the atrium will also serve as the corridor wall at the 2nd floor. The  variance request is to permit the wall to be constructed as a smoke partition with windows in  a gasketed frame and protected by a sprinkler in lieu of fire-rated corridor construction. 

The building is a new4-story assisted living facility, I-1 Occupancy. The building is 4-stories  and Type VA Construction. The building is protected throughout with an automatic sprinkler  system in accordance with NFPA 13.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. The building will be protected throughout with an automatic sprinkler system in accordance  with NFPA 13.

2. A fire alarm system will be installed throughout the building.

3. Smoke detection will be provided throughout the corridors and areas open to the corridor.

4. Protecting the opening as required for an atrium is not adverse to public health, welfare, or  safety. 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: The hardship is the cost to provide rated openings in wall that is protected as required for an  atrium in a building protected throughout with an NFPA 13 sprinkler system. The owner wishes to maintain the openness of this portion of the building to help make the assisted living facility  feel less institutional. 

Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IBC, 1405.6 
Conditions:  ACI 530/ASCE 5/TMS 402, 6.2.2.3.1.3

The code permits anchored masonry veneer with a backing of cold-formed steel framing to  be a height of 30 feet above a noncombustible foundation. The code requires the weight of  any anchored masonry veneer above this height to be supported by noncombustible  construction for each story above 30 feet in height from the noncombustible foundation.  

The proposed height of the veneer above the noncombustible structural support system is  approximately 38 feet. 

The building is a new 4-story assisted living facility, I-1 Occupancy. The building is 4-stories and Type VA Construction. The building is protected throughout with an automatic sprinkler  system in accordance with NFPA 13. 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: According to the attached letter and analysis from the structural engineer the proposed  design is acceptable and will not be adverse to safety. 

This variance has been granted for other similar projects including: 14-04-19(d), 12-09-33(a), 10-11-24, 08-06-02, 08-04-07(d), 07-09-31, and 06-11-58(d). 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
 
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: The veneer height has been designed using the alternative design of anchored masonry  veneer to justify construction taller than 30 feet. It is a cost hardship to provide relief at each  story above 30 feet when it has been designed to comply with code.