Project Information
Concord High School 2018 Addition
59117 Minuteman Way
Elkhart IN 46517
County ELKHART
Project Type New   Addition Y Alteration   Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 5742945471 Email: [email protected]
Local Fire Official 
5742945471 Email: [email protected]
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
3311.2, 2014 IFC
Conditions: The proposed addition will impact means of egress in the existing building during the time of  construction.  The project will begin in June, 2018, and is scheduled to be complete during  the summer of 2019.

The addition will have approximately 30,440 sq ft + a mezzanine of approximately 2,080 sq ft.
The addition will include classrooms, computer and maker labs, and rest rooms. The  addition
will be classified as E Occupancy and Type IIB Construction.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. Sec. 3311.2, exception, IFC, states that; approved temporary means of egress systems
and facilities may be provided during construction.  

2. Exit lighting and signage will be adjusted as necessary to accommodate the planned
modifications to the egress system.

3. Fire drills will be conducted to familiarize students and faculty of the revised egress
routes as indicated.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: Imposition of the rule would require relocating a number of departments off-site during  construction.