Owner / Applicant Information
Wade Conner
Trinity Metals, LLC
6400 ENGLISH AVE
INDIANAPOLIS IN 46219
Phone 3173588265
Email [email protected]
Submitter Information
Carrie Ballinger
RTM Consultants, Inc.
6640 Parkdale Place, Ste J
Indianapolis IN  
Phone 3173297700
Email [email protected]
Designer Information
Jerry Hoffman
US Architects
9200 W Smith Street
Yorktown IN  
Phone 7654051220
Email [email protected]
Project Information
Trinity Metals Addition
6400 English Ave
Indianapolis IN 46219
County MARION
Project Type New   Addition Y Alteration   Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 3173278700 Email: [email protected]
Local Fire Official 
3173278700 Email: [email protected]
Phone:


Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IBC Sec. 503
Conditions: A new addition along with existing building will exceed allowable area for Type IIB  Construction.  The allowable area is 126,500 square feet.  The total building area with  addition will be approximately 138,433 square feet.

The project involves a new 18,000sf addition to an existing 120,433sf scrap metal processing  facility. The existing building and addition are classified Type IIB Construction and F-2  Occupancy.   
 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. The addition will be provided with an automatic sprinkler system throughout.  The existing  building is protected with an automatic sprinkler system throughout.

2. The existing building and addition are noncombustible construction and contents are  noncombustible metals.

3. The building is surrounded with over 60 feet of open space on 2 sides, and at least 30 feet  of open space on all sides.

4. The local zoning ordinance requires a minimum side/rear yard set back of 30 feet in the  industrial district.  Development of the neighboring lot would require 30 feet from the adjoining  property line, resulting in minimum of 60 feet between buildings.

5. Based upon the open space provided and setback requirements, noncombustible  construction, and sprinklers throughout the addition and existing building, the increase in  allowable area will not be adverse to safety.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
  Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
Facts: The area being enclosed is an existing scrap metal sorting area.  The EPA and IDEM are  requiring the sorting area to be enclosed in order to stop water run-off from the current  sorting area.  It is a cost and operational hardship to provide a new fire wall between the  existing building and sorting area being enclosed, while a noncombustible addition with  sprinklers provided will not be adverse to safety.
Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IFC Sec. 507.5.1
Conditions: A fire hydrant will not be provided within 600 feet of the new addition. 

The project involves a new 18,000sf addition to an existing 120,433sf scrap metal processing  facility. The existing building and addition are classified Type IIB Construction and F-2  Occupancy.   

Conditions: A fire hydrant will not be provided within 600 feet of the new addition. 

The project involves a new 18,000sf addition to an existing 120,433sf scrap metal processing  facility. The existing building and addition are classified Type IIB Construction and F-2  Occupancy.   
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. Two hydrants are existing on site within 1,000 feet of the addition.

2. The addition will be provided with an automatic sprinkler system throughout.  The existing  building is protected with an automatic sprinkler system throughout.

3. The existing building and addition are noncombustible consturction and contents are  noncombustible metals.

4. Fire extinguishers will be provided in the addition.
 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: The area being enclosed is an existing scrap metal sorting area.  The EPA and IDEM are  requiring the sorting area to be enclosed in order to stop water run-off from the current  sorting area.  It is a cost hardship to provide a private hydrant within 600 feet of the addition,  while there are two existing hydrants on site within 1,000 feet and sprinklers will be provided  throughout the addition.