Owner / Applicant Information
Niki Balish
Town of Bargersville
24 NORTH MAIN STREET
BARGERSVILLE IN 46106
Phone 3174225115
Email [email protected]
Submitter Information
Edwin Rensink
RTM Consultants Inc
6640 Parkdale Place
Indianapolis IN  
Phone 3173297700
Email [email protected]
Designer Information
Mac McCauley
Strand Associates, Inc
629 Washington Street
Columbus IN  
Phone 8123729911
Email [email protected]
Project Information
Bargersville Waste Water Treatment Plant Chemical Building
500 West Old School Street
Bargersville IN 46106
County JOHNSON
Project Type New Y Addition   Alteration   Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 3174225115 Email: [email protected]
Local Fire Official 
3174225115 Email: [email protected]
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
903.2.5.1, 2014 IBC
Conditions: Automatic sprinkler protection will not be provided for the 660 sq ft chemical storage room,  classified as H-4 Occupancy due to storage of a corrosive water treatment chemical in  excess of the 500-gallon exempt amount.  

The storage tanks will store a 50% solution of aluminum sulfate.  Building is classified as F-2  and H-4 Occupancies.
 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. Aluminum sulfate is a noncombustible material. The room will include metering pumps,
and associated piping. There is no fire hazard involved.
2. The room will be separated from the remainder of the building with a 2-hour occupancy  separation, as required.
3. Based upon lack of any fire hazard for the room contents and separation from the rest of
the building, the lack of sprinkler protection will not be adverse to safety. 
4. Dozens of similar variances have been granted previously for water treatment facilities over  at least the past 15 years, including 05-03-20, 06-04-30, 08-05-39, 10-11-25, 26, 27, 28, 29,  and 30, 11-08-24, 11-12-05, 12-05-27, 12-05-30, 13-08-61, 14-04-40, 14-05-34, 14-07-26, 14- 07-29, 15-01-03, 15-09-75, 15-10-13, 16-05-55, 17-03-52, 17-04-73, and 17-12-51.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: The hardship is the cost of installing and maintaining an automatic sprinkler protection in a  room without a fire hazard. In this case, the sprinkler system would not add any benefit to  safety.