Owner / Applicant Information
Douglas M Morris
Butler University -Operations Division
451 WEST 52ND STREET
INDIANAPOLIS IN 46208
Phone 3179409443
Email [email protected]
Submitter Information
Christina    Collester
RTM Consultants, Inc.
6640 Parkdale Place
Indianapolis IN  
Phone 3173297700
Email [email protected]
Project Information
Butler University Police Station
525 W. Hampton Dr.
Indianapolis IN 46208
County MARION
Project Type New   Addition   Alteration   Existing Y Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order?    
Violation Issued by: NA
Local Building Official
Phone: 3173275549 Email: [email protected]
Local Fire Official 
Phone: 3173275549 Email: [email protected]

Variance Details
Code Name:  Other Code (Not in the list provided)
2010 NFPA 72 26.6.3.2.1.4
Conditions: The Proprietary Supervising Station for this campus does not employ two different types of  transition means for communication between the local building systems and proprietary  supervising station.
 
 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: The local building fire alarm systems for new and existing buildings send trouble, supervisory and alarm notification to the Proprietary Supervising Station located on Butler University  Campus at the police department dispatcher, a constantly attended location using a  redundant fiber optic cable. 

The redundant fiber optic cable provides an alternate routing between buildings should a
primary path be broken or disrupted.

Indiana deletes section 26.6.3.1.4.1 from the model code which is the section that permits this  technology for a campus reporting system. This system is supervised and would report  failure within the 5 minutes as required by this section. 

Once this section is deleted two different technologies would be required to communicate with the Proprietary Supervising station. 
 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: This system is reliable and redundant and meets the requirements of the model code. It is a  system widely used for campus fire alarm systems. Requiring a Telephone transmission lines for new and existing buildings is an additional cost maintenance item.