Project Information
Hampton Inn & Suites
Harrison Square - Jefferson Blvd and Harrison St
Fort Wayne IN 46802
County ALLEN
Project Type New Y Addition   Alteration   Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 2604997131 Email: [email protected]
Local Fire Official 
2604997131 Email: [email protected]
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
Table 601, 2014 IBC
Conditions: The roof steel and supporting elements for the exterior entry canopy and the small rear  enclosed vestibule (170 sq ft) will not be fire-rated.  Based upon the Type IB Construction  Type required, the structure is required to be 1-hour rated.
The project involves construction of a 7-story hotel, with amenity spaces and service  functions
on the 1st floor and the the bar and fitness area on 7th floor. Guest rooms are located on
floors 2-7.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.  The exterior canopy is provided only for weather shelter for people entering and leaving  the front lobby of the building.  There is no fuel load under the canopy.
2.  Sprinkler protection will be provided in the enclosed 1st floor vestibule as required.
3.  Similar variances for exterior canopies and vestibules have been previously approved,  including 18-02-25b, 17-12-54d, and 16-01-28b.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: The hardship is cost to fireproof areas with little or no combustible fire load, and in the case of the front canopy, an exterior space.

Variance Details
Code Name:  Other Code (Not in the list provided)
Table 601, 2014 IBC
Conditions: Roof steel over the 7th floor will be of unprotected noncombustible construction. Based
upon Type IB Construction required, the roof is required to be 1-hour rated.
The project involves construction of a 7-story hotel, with amenity spaces and service  functions
on the 1st floor and the the bar and fitness area on 7th floor. Guest rooms are located on
floors 2-7.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. The building will be protected throughout with an automatic sprinkler system per NFPA 13.
The sprinkler system on the 7th floor will be provided with a design density increase of 100%
above the minimum required for light hazard occupancy - 0.2 gpm per sq ft in lieu of the
minimum 0.1 gpm per sq ft. Sprinklers will be at light hazard spacing.
2. Automatic sprinkler protection is an effective method of ensuring structural fire-resistance  by limiting fire size and the heat release rate, and therefore significantly limiting the effects of  fire. The use of enhanced sprinkler protection will provide an additional safety factor for the  unprotected roof structure.  
3.  Similar variances for nonrated roof structure have been approved based upon enhanced  sprinkler protection, including 17-12-54d, 17-06-24a, 17-05-43a, 16-03-53, 15-11-11c, 15-01- 28a, and 14-03-15c.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
  Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
Facts: The use of unprotected roof steel is designed to create the desired effect of exposed  structure on the 7th floor as well as achieve cost savings.
Variance Details
Code Name:  Other Code (Not in the list provided)
Table 601, 2014 IBC
Conditions: Roof steel over the 7th floor bar will be of unprotected noncombustible construction.  Based  upon Type IB Construction required, the roof is required to be 1-hour rated.

The project involves construction of a 7-story hotel, with amenity spaces and service  functions on the 1st floor and the the bar and fitness area on 7th floor.  Guest rooms are  located on floors 2-7.  
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).

2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.  The building will be protected throughout with an automatic sprinkler system per NFPA 13.   The sprinkler system in the bar space will be provided with a design density increase of 100% above the minimum required for light hazard occupancy - 0.2 gpm per sq ft in lieu of the  minimum 0.1 gpm per sq ft.  Sprinklers will be at light hazard spacing.
3. Automatic sprinkler protection is an effective method of ensuring structural fire-resistance  by limiting fire size and the heat release rate, and therefore significantly limiting the effects of  fire. The use of enhanced sprinkler protection will provide an additional safety factor for the  unprotected roof structure. Historical fire records indicate that a properly designed,  maintained and supervised sprinkler system is virtually 100% successful in controlling fires in  buildings of light or ordinary hazard occupancy.  Modern building and fire codes require a  rigorous maintenance program for sprinkler systems, and also require electrical supervision  of sprinkler valves controlling the water supply - lack of these features have historically been  the cause of sprinkler failures where the sprinkler design matches the hazard of the building.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
  Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
Facts: The use of unprotected roof steel is desired to match the unprotected roof overhang over the  outdoor patio area.

Variance Details
Code Name:  Other Code (Not in the list provided)
 
Conditions:  
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
 
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts:  
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: