Owner / Applicant Information
John Allen
Allen Trucking 
2989 INDUSTRIAL BLVD
CRAWFORDSVILLE IN 47933
Phone 8883640828
Email [email protected]
Submitter Information
Melissa Tupper
RTM Consultants, Inc.
6640 Parkdale Place
Indianapolis IN  
Phone 3173297700
Email [email protected]
Designer Information
Alan  Schambach
FBi Buildings, Inc.
3823 W. 1800 S.
Remington IN  
Phone 2199641040
Email [email protected]
Project Information
Allen Trucking New Building
2989 Industrial Blvd
Crawfordsville IN 47933
County MONTGOMERY
Project Type New Y Addition   Alteration   Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order?    
Violation Issued by: NA
Local Building Official
Phone: 7653645152 Email: [email protected]
Local Fire Official 
7653645152 Email: [email protected] 
Phone:


Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IBC, 903.2.9.1
Conditions: A commercial vehicle maintenance shop will have a fire area of approximately 6,912 square  feet in area. Code limits the fire area of buildings used for the storage or repair of commercial vehicles to 5,000 square feet. Buildings with fire areas over 5,000 square feet must be  sprinklered or divided into fire areas less than 5,000 square feet by 3-hour fire barriers. 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. The office area will be separated from the shop by a 1-hour fire partition.

2. A fire alarm system will be installed in the building.

3. Smoke detectors will be provided in the office and heat detectors will be provided in the  shop, tied to the fire alarm system. 

4. The maximum travel distance to an exit is approximately 71 feet, code permits 200 feet. 

5. The building sits on a large lot, it is over 100 from the road and over 250 feet form the  nearest property line.

6. This project has been reviewed with the local fire department and they are not opposed to  the variance. 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
 
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: It is a cost hardship to install a 3-hour rated fire barrier to divide the building into fire areas  less than 5,000 square feet. The cost of the wall is estimated at $45,000-$50,000. The cost to  construct the building is $225,000.