Owner / Applicant Information
Rick Kinney
Even Keel Event Productions, LLC
1808 BLUFFTON ROAD
FORT WAYNE IN 46809
Phone 2604428181
Email [email protected]
Submitter Information
Melissa Tupper
RTM Consultants, Inc.
6640 Parkdale Place
Indianapolis IN  
Phone 3173297700
Email [email protected]
Designer Information
JAMES R KRATZAT
MSKTD & Associates, Inc.
1715 Magnavox Way
Fort Wayne IN  
Phone 2604329337
Email [email protected]
Project Information
Clyde Theatre Renovation
1808 Bluffton Rd
FORT WAYNE IN 46809
County ALLEN
Project Type New   Addition   Alteration Y Existing   Change of Occupancy  
Project Status F F=Filed U or Null=Unfiled
IDHS Issued Correction order?    
Violation Issued by: NA
Local Building Official
Phone: 2604497672 Email: [email protected]
Local Fire Official 
2604497672 Email: [email protected]
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IFC, 901.6
Conditions: The theater will have concerts and events where smoke, fog, and haze is used (excludes  pyrotechnics). The variance request is to permit the theater to put the smoke detection  system in event mode during these performances. Code requires systems to be maintained  in an operative condition at all times.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. A rate of rise heat detection system will be provided in the stage area which will remain  operational at all times, this is not required by code. 

2. The building is protected throughout with an automatic sprinkler system per NFPA 13. The  sprinkler system will remain operational at all times.

3. A person will monitor the fire alarm panel and will be able take the system out of event mode if necessary. 

4. This has been reviewed with the local fire and building official, and they are not opposed to  the variance. 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
  Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
Facts: It is an operational hardship to keep the smoke detectors near the stage operational when  there are performances involving smoke, fog, or haze due to the false alarms that would  result.