Owner / Applicant Information
Todd McDonald
Adams Central Community Schools
222 W. WASHINGTON STREET
MONROE IN 46772
Phone 2606921045
Email [email protected]
Submitter Information
Melissa Tupper
RTM Consultants, Inc.
6640 Parkdale Place
Indianapolis IN  
Phone 3173297700
Email [email protected]
Designer Information
Kevin Scully
Design Collaborative, Inc.
200 East Main Street
Fort Wayne IN  
Phone 2604224241
Email [email protected]
Project Information
Adams Central Community Schools
222 W. Washington Street
Monroe IN 46772
County ADAMS
Project Type New   Addition Y Alteration Y Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order?    
Violation Issued by: NA
Local Building Official
Phone: 2607245305 Email: [email protected]
Local Fire Official 
2607245305 Email: [email protected]
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IFC, 3311.2
Conditions: The code requires means of egress to be maintained during construction and demolition,  remodeling or alterations and additions to any building. The existing exterior exit, indicated  on the attached drawing, will be closed during the construction of Phase 2. Closing the exit  will create a temporary dead end of approximately 28 feet. The request for temporary means  of egress as described will be from March 1, 2018 - January 31, 2019. 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.   Sec. 3311.2, exception, IFC, states that ¿approved temporary means of egress systems  and facilities¿ may be provided during construction. 

2.  A temporary wall will be constructed to reduce the dead end corridor from 59 feet to  approximately 28 feet. Based upon a corridor width of 10 feet, a maximum dead end of 25 feet  is permitted. 

3.  The travel distance to an exit will not exceed that permitted by code, 200 feet. 

4.  Exit lighting and signage will be adjusted as necessary to accommodate the planned  modifications to the egress system. 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
Y
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: The use of temporary means of egress provisions will permit the use of existing building  areas during construction. It is not feasible to provide a complying corridor configuration or to  maintain the existing exit during construction of the addition.

Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IBC, 706 
Conditions: The classroom and gymnasium additions will be separated from the existing school with a 2- hour fire barrier in lieu of a 4-hour structurally independent fire wall. A 4-hour fire wall is  required based upon the date of the last addition to the building (1987). 

The project involves a classroom addition (38,815 sf), a gymnasium addition (31,156 sf), and  the renovation of portions of the existing school. 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.  The additions will be protected throughout with an automatic sprinkler system per NFPA 13. 

2.  The additions will be structurally independent of the existing building. 

3.  Variance 10-09-39(a) was granted for this school to permit the 2010 addition to be  separated by a 2-hour fire barrier in lieu of a 4-hour fire wall. Similar variances have been  granted in the past. 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
 
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
  Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
Facts: It is cost hardship to provide a separate fire wall that complies with the structural stability  requirement. 
Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IBC, 1018.1
Conditions: A portion of the existing school will be renovated. The variance request is to permit the new  corridors within the renovated areas to be non-rated. Code requires new corridors to be 1- hour rated when the building is not sprinklered throughout. See attached plans for details.

The project involves a classroom addition (38,815 sf), a gymnasium addition (31,156 sf), and  the renovation of portions of the existing school.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. The area being renovated, including adjoining corridors, will be sprinklered per NFPA 13. 

2. The lack of rated corridors is not be adverse to safety based upon the rooms and corridors egress corridors being sprinklered. 

3.   Variance 10-09-39(c) was granted for this school to permit the non-rated corridors in  portions of the building renovated 2010 based upon sprinklers being added to the renovated  areas.

Facts: 1. The area being renovated, including adjoining corridors, will be sprinklered per NFPA 13. 

2. The lack of rated corridors is not be adverse to safety based upon the rooms and corridors egress corridors being sprinklered. 

3.   Variance 10-09-39(c) was granted for this school to permit the non-rated corridors in  portions of the building renovated 2010 based upon sprinklers being added to the renovated  areas.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
 
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: The owner¿s undue hardship is the cost to provide 1-hour rated corridor walls and 20-minute rated doors with closers when this portion of the building is sprinklered.