Owner / Applicant Information
Eric Atkins
Archdiocese of Indianapolis
1400 NORTH MERIDIAN STREET 
INDIANAPOLIS IN 46206
Phone 3172361453
Email [email protected]
Submitter Information
Edwin Rensink
RTM Consultants Inc
6640 Parkdale Place
Indianapolis IN  
Phone 3173297700
Email [email protected]
Designer Information
Michael Eagan
Entheos Architects
802 Lord Street
Indianapolis IN  
Phone 3179519590
Email [email protected]
Project Information
Nativity Catholic Church Addition and Renovation
7225 Southeastern Avenue 
Indianapolis IN 46239
County MARION
Project Type New   Addition Y Alteration Y Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 3173275544 Email: [email protected]
Local Fire Official 
3173275544 Email: [email protected]
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
507.5.1, 2014 IFC
Conditions: A fire hydrant connected to a water supply is not provided within 400 feet of the proposed  5,513 sq ft Narthex addition to the existing church worship facility.
    
The project also includes renovation of the existing worship space.  The building will be  classified as A-3 Occupancy and Type VA Construction. 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.   The building will be provided with a monitored fire alarm system.
2.   Smoke detection will be provided throughout the addition, and in the existing mechanical  rooms, storage room, and sacristy.  The detectors will be connected to the fire alarm system,  providing a method of automatic alarm in the event of fire.
3. A total of five (5) exits will be provided from the existing worship space - there are three (3)  existing.  
4. The same variance was granted for the adjacent Fellowship Hall in 2013 (13-04-30a).  A  similar variance was granted for Eastside Hispanic SDA Church in May, 2017 (17-05-56).   Other similar variances for buildings other than churches have been approved in  Indianapolis, including 14-01-40a, 14-12-46, 15-10-18, 16-10-16, and 16-12-49. 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
Y
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
  Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
Facts: The nearest public water supply capable of supplying a fire hydrant is approximately 3,000  feet from the site.  The estimate for extending the public water line to the site to supply a  private hydrant is $420,000, which does not include the cost of shutdown of city streets and  other associated costs. The estimate for extending the public water line to the site to supply a  private hydrant is $420,000

Variance Details
Code Name:  Other Code (Not in the list provided)
903.2.1.3, 2014 IBC
Conditions: An automatic sprinkler system will not be provided for the addition + existing building.  The  project scope includes a Narthex addition of 5,513 sq ft to the existing worship facility of  11,402 sq ft.  An automatic sprinkler system is required based upon a combined fire area  exceeding 7,000 sq ft.
    
The project also includes renovation of the existing worship space.  The building will be  classified as A-3 Occupancy and Type VA Construction. 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.   The building will be provided with a monitored fire alarm system.
2.   Smoke detection will be provided throughout the addition, and in the existing mechanical  rooms, storage room, and sacristy.  The detectors will be connected to the fire alarm system,  providing a method of automatic alarm in the event of fire.
3. A total of five (5) exits will be provided from the existing worship space - there are three (3)  existing.  
4. Three (3) exterior exits will be provided from the Narthex addition - maximum travel distance to an exterior exit from the addition will be 80 feet, less than the code permitted maximum of  200 feet.
5. The Narthex does not increase the actual occupant load of the building, since it is  occupied only as a means of arrival or departure from the worship space.
6. Previous similar variances have been granted for Narthex additions to existing churches,  including St Paul Catholic Church (16-06-40), St Jude Parish Catholic Church (13-06-04), and  Immaculate Conception Catholic Church (11-04-32).
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
Y
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: A public water supply is not available.  The estimate for installation of an on-site water supply  and sprinkler system for the existing building and addition is $135,000.