Project Information
St. Michael Catholic Church
519 Jefferson Boulevard
Greenfield IN 46140
County HANCOCK
Project Type New   Addition Y Alteration   Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 3174774320 Email: [email protected]
Local Fire Official 
3174774320 Email: [email protected]
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IBC 903.2.1.3/707.3.10
Conditions: An existing A-3 Occupancy Type VB construction church of 7,206 square feet will have 1,119  square feet removed and 4,157 square feet added for new circulation space, restrooms and  support areas. No additional occupant load is calculated for this expansion.  The net  increase of square feet to building is 3,038 square for a total area of 9,125 square feet. The  fire area is under 12,000 square feet, but the existing occupant load of the building is 419  occupants and based upon new construction would require a fire suppression system or a  2-hour fire barrier separation between sanctuary and new circulation space. 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. The addition increases exit width, number of exits from 3 to 4, and means of egress flow for  the building and provides new accessible restrooms.
2. A Monitored fire alarm and smoke alarm system will be provided throughout existing and  new floor areas. 
3. The addition and existing square feet is still within allowable area limitations per Table 503  IBC and fire area per Section 
    903.2.1.3 Item 1.
4. Last similar variance approved for this issue for J &T was variance # 16-09-40.
 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: The owner's undue hardship involves the need to increase the circulation space for the  means of egress and provide accessible restrooms for the building. A fire barrier separation  would make the expansion not feasible and cost prohibitive.