Project Information
Marott Center Addition
350 Massachusetts Ave
 
INDIANAPOLIS IN 46204
County MARION
Project Type New   Addition Y Alteration   Existing   Change of Occupancy  
Project Status F F=Filed U or Null=Unfiled
IDHS Issued Correction order? No yes
Violation Issued by: LBD
Local Building Official
Phone: 3173275544 Email: [email protected]
Local Fire Official 
3173275544 Email: [email protected]
Phone:

Variance Details
Code Name: 2012 Indiana Plumbing Cod, (675 IAC 16-1.4)
802.3
Conditions: The receptor for the condensate hub drain from above-ceiling air conditioning units has  been cited for for not having ready access by virtue of its location above a ceiling, requiring  ladder access.  The small hub drain serves as a receptor for condensate for above-ceiling  fan coil units in the white box office tenant spaces in the building.
   
The project involves construction of a 4-story addition to the existing Marott Center building.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1.     As explained in the attached letter from the engineer of record, the condensate disposal  from air conditioning units is addressed specifically in Sec. 314.2.1, IPC, and the engineer  further contends that Chapter 8 applies to indirect/special waste from food handling  equipment and other similar applications - and does not apply to a condensate drain from  air-conditioning units.  As such, the requirements for ready access, i.e., no ladder access,  in Chapter 8 for special/indirect wastes should not be applied to condensate drains from air- conditioning units.
2. The proposed method of access is no different than that provided for quarterly filter  changes for the fan coil units or for accessing plumbing cleanouts located above the ceiling.  Access to the drain will be provided by way of a ceiling panel, and can be reached with a  standard step ladder by maintenance personnel.
 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
 
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: There is no feasible way to provide drain access at floor level in this case, since this is an  open room without dividing walls.